Product Details

The ABB PSM0004 2RCA025059A0001R, also cataloged as the PSM0004 Power Supply Module, operates as a dedicated hardware component for power regulation and internal DC voltage distribution within ABB Relion 615 and 620 series protection relays. The module converts wide-range AC and DC auxiliary supply voltages into filtered, regulated internal power rails, driving relay processing units and output logic circuits under continuous operation.

Hardware Specifications

Parameter Specification
Model PSM0004
Brand ABB
Part Numbers 2RCA025059A0001R / 2RCA024585P
Dimensions 125 x 100 x 60 mm
Weight 0.5 kg
Input Voltage Range 100-240 V AC (50/60 Hz) or 48-250 V DC
Protection Functions Overload, over-voltage, short-circuit protection
Compatible Platforms ABB Relion 615 / 620 Series Relays (REF615, RET615, RED615, REM615)
Operating Temp -25 deg C to +55 deg C
Power Consumption Max 25 W (internal conversion dissipation profile)
Origin Finland

Firmware Flash Compatibility & Internal Bus Power Delivery

The PSM0004 power supply module incorporates deterministic power delivery architecture designed to stabilize processing logic during auxiliary supply transients. Integrated regulation circuits interface directly with the relay backplane bus to deliver ripple-free DC rails to processing hardware. Firmware flash compatibility across the ABB Relion architecture ensures uncorrupted parameter memory retention in non-volatile flash storage during sudden input power interruptions or voltage sags.

Frequently Asked Questions

Q: What happens if an over-voltage surge occurs on the AC/DC supply input terminals?

A: The onboard protection circuit clamps transient over-voltage conditions and limits current draw, preventing damage to downstream internal processing boards and relay logic.

Q: Can the PSM0004 power supply board be hot-swapped while the protection relay is energized?

A: No. Auxiliary input power must be completely disconnected and isolated from the terminal block prior to extracting or inserting the module to prevent electrical damage to backplane pin headers.

Q: How does the PSM0004 indicate internal power fault conditions to the main CPU module?

A: The module reports internal supply rail drops or short-circuit states through dedicated backplane status lines, triggering a self-supervision watchdog signal on the front display.

Field Installation Guidelines

Observe the following procedures when installing or replacing the power supply unit:

  1. Electrical Isolation: De-energize all AC and DC auxiliary power sources connected to the relay cabinet terminals. Confirm zero voltage using a calibrated multimeter.
  2. Electrostatic Protection: Wear a grounded anti-static wrist strap before handling the replacement module. Hold the assembly by its plastic edges to avoid touching exposed board traces.
  3. Module Alignment: Align the PSM0004 card edges with the internal guide slots of the Relion relay chassis. Slide the board inward until the backplane multi-pin header fully seats.
  4. Terminal Securing: Tighten the rear panel retaining screws to 0.6 N-m to ensure structural stability and continuous protective earth ground contact.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Modern control systems rely heavily on seamless interprocess communication to exchange operational data between software programs. Microsoft first introduced the Dynamic Data Exchange (DDE) protocol in 1987 to enable real-time data sharing. In factory automation, DDE served as an early bridge between control software and Windows desktop applications. Therefore, understanding DDE mechanics provides crucial insights into how legacy industrial networks established software-level connectivity.

Read more
Demystifying CPU Communication Ports in Siemens PLC Architectures

Demystifying CPU Communication Ports in Siemens PLC Architectures

Industrial automation relies heavily on robust data exchange between devices. Without seamless connectivity, field instruments, network switches, human-machine interfaces, and programmable logic controllers cannot coordinate effectively. Therefore, understanding the various CPU communication ports available in Siemens hardware ensures efficient factory automation design and seamless system integration.

Read more
Mastering the Siemens PLC Scan Cycle: How the CPU Executes Automation Programs

Mastering the Siemens PLC Scan Cycle: How the CPU Executes Automation Programs

Industrial automation relies heavily on programmable logic controllers (PLCs) to manage complex manufacturing processes. Many engineers dive straight into programming without mastering the underlying architecture. However, understanding how a PLC CPU executes a program ensures reliable system design. Therefore, mastering the scan cycle optimizes both performance and troubleshooting in modern control systems.

Read more