Product Details

The GE IS200STAIH2ABB, also cataloged as the IS200STAIH2ABB Simplex Analog Input Terminal Board, operates as a dedicated hardware component for localized analog field signal processing and loop distribution within GE Mark VIe control system platforms. Configured to interface directly with two-wire, three-wire, four-wire, and externally powered transmitters, the board converts physical process variables into digitized data pathways across the system I/O network.

Hardware Specifications

Parameter Specification
Model IS200STAIH2ABB
Brand GE
Origin USA
Dimensions 15.9 cm x 10.2 cm
Operating Temp -30 to +65 deg C
Power Consumption Standard Backplane Bus Draw
Product Type Analog Input Terminal Boards
Analog Inputs 10 channels
Analog Outputs 2 channels (0-20 mA jumper-configurable, 1 supports 0-200 mA)
Max Lead Resistance 15 ohms
Mounting Type DIN rail mounting with sheet metal carrier and plastic insulators

Backplane Bus Communication Velocity and Density Scaling

The GE IS200STAIH2ABB integrates Euro-block termination hardware with internal trace routing to maintain high backplane bus communication velocity and minimize noise coupling on sensitive 4-20 mA circuits. Onboard ID chip technology automatically transmits board identification and hardware revision data to the active I/O pack, enabling real-time diagnostic tracking, optimized I/O density scaling, and continuous firmware flash compatibility across the Mark VIe network frame.

Frequently Asked Questions

Q: How is the high-current 0-200 mA analog output channel configured on the IS200STAIH2ABB?

A: Output current range selection is managed via physical onboard jumpers that reconfigure output drive circuitry between standard 0-20 mA mode and the 0-200 mA high-current threshold.

Q: How does the onboard ID chip function within the Mark VIe system?

A: The ID chip holds hardcoded board type, serial number, and revision status data, which the connected I/O pack reads upon power-up to validate system hardware configuration automatically.

Q: What transmitter power wiring configurations are natively supported by this terminal board?

A: The board supports two-wire, three-wire, and four-wire field transmitters, as well as self-powered external instrumentation loops, directly through its Euro-block terminal connections.

Field Installation Guidelines

  1. Disconnect all power feeds to the Mark VIe cabinet and verify zero voltage across field terminal connections before installing the board.
  2. Snap the sheet metal carrier with its plastic insulating base securely onto the 35 mm DIN rail within the I/O cabinet.
  3. Tighten ground strap connections to establish a solid ground path from the metal carrier frame to the cabinet enclosure.
  4. Route field sensor cables through cable trays, stripping wire ends and securing conductors into the Euro-block screw terminals while observing maximum 15 ohm lead resistance limits.
  5. Connect the dedicated I/O pack onto the board D-sub interface connectors and ensure locking screws are fully tightened before applying power.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Comprehensive Guide to PLC Types in Modern Industrial Automation

Comprehensive Guide to PLC Types in Modern Industrial Automation

Modern industrial automation relies on programmable logic controllers to govern critical factory operations. System integrators classify PLCs based on scale, hardware architecture, and power supply design. Understanding these core categories enables automation engineers to select the right control system architecture. Consequently, proper hardware selection optimizes performance while minimizing long-term operational costs.

Read more
Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Modern control systems rely heavily on seamless interprocess communication to exchange operational data between software programs. Microsoft first introduced the Dynamic Data Exchange (DDE) protocol in 1987 to enable real-time data sharing. In factory automation, DDE served as an early bridge between control software and Windows desktop applications. Therefore, understanding DDE mechanics provides crucial insights into how legacy industrial networks established software-level connectivity.

Read more
Demystifying CPU Communication Ports in Siemens PLC Architectures

Demystifying CPU Communication Ports in Siemens PLC Architectures

Industrial automation relies heavily on robust data exchange between devices. Without seamless connectivity, field instruments, network switches, human-machine interfaces, and programmable logic controllers cannot coordinate effectively. Therefore, understanding the various CPU communication ports available in Siemens hardware ensures efficient factory automation design and seamless system integration.

Read more