PRODUCT SKU : IC694MDL240

PRODUCT TYPE : AC Input Module

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Description

The IC694MDL240 is a 120 Volt AC input module from GE Fanuc Emerson designed for use with the PACSystem RX3i. This discrete input module provides 16 input channels that are ideal for industrial automation applications requiring precise signal monitoring. The IC694MDL240 is engineered for high reliability, with excellent input signal range, rapid response times, and superior isolation features.

Technical Specifications

  • Manufacturer: GE Fanuc Emerson

  • Product Type: Input Module

  • Part Number: IC694MDL240

  • Product Line: PACSystem RX3i

  • Weight: 0.56 lbs (0.26 kg)

Key Features

  • Input Channels: 16 (single group of 16 inputs)

  • Nominal Input Voltage: 0-120 VAC

  • Input Signal Range: 0-132 VAC

  • Current Draw: 90 mA (all inputs active)

  • Input Frequency: 47-63 Hz

  • Input Current per Channel: 12 mA

  • On State Voltage: 74 VAC to 132 VAC

  • Off State Voltage: 0 to 20 VAC

  • On State Current: 6 mA

  • Off State Current: 2.2 mA

  • Response Times:

    • On Response Time (Typical): 30 ms

    • Off Response Time (Maximum): 45 ms

  • Input Impedance: 250 ohms

  • Power Consumption: 90 mA

  • Bus Voltage: 5 Volts

  • Isolation: Optical and channel isolation 250V continuous, 1500 VAC for 1 minute

  • Temperature Range:

    • Operating: 0°C to 60°C

    • Storage: -40°C to 85°C

  • Operating Humidity: 80% (Non-Condensing)

  • Product Lifecycle: Active

Applications and Use Cases

The IC694MDL240 is perfect for discrete input signal applications such as monitoring digital switches, sensors, and other low-voltage AC devices in industrial control systems. It’s an ideal choice for factory automation where reliable performance and efficient monitoring of AC signals are crucial.

FAQ

Q: How many channels does the IC694MDL240 have for input signals?
A: The IC694MDL240 supports 16 input channels.

Q: What is the typical on-state voltage for the input module?
A: The on-state voltage for the IC694MDL240 ranges from 74 VAC to 132 VAC.

Q: What is the response time for an input signal to turn on?
A: The on response time is typically 30 ms.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more
Mastering Wire Identification in Industrial Automation: The Power of Ferrules and Cross-Ferruling

Mastering Wire Identification in Industrial Automation: The Power of Ferrules and Cross-Ferruling

Proper wire labeling forms the cornerstone of reliable control system installation and long-term maintenance. In complex industrial automation environments, technicians terminate thousands of conductor ends inside control panels, marshalling racks, and field junction boxes. Ferrules serve as individual tube-shaped sleeve markers slipped onto conductors before final termination. While technicians historically relied on pre-printed individual letter rings, modern control panel builders utilize automated ferrule printing machines. These thermal-transfer printers generate durable, single-sleeve heat-shrink tags directly matching approved wiring schematics, significantly accelerating cabinet assembly workflows.

Read more
Understanding Marshalling Cabinets in Industrial Automation and Control Systems

Understanding Marshalling Cabinets in Industrial Automation and Control Systems

Marshalling cabinets serve as the crucial connection hub between field instruments and centralized processing units. In large DCS and PLC control system architectures, hundreds of multipair field cables run from local junction boxes to the central instrument equipment room. The marshalling cabinet houses field terminal blocks, surge arresters, intrinsic safety isolation barriers, and interposing relays. By segregating field field-wiring terminations from sensitive processor hardware, engineers protect expensive controller backplanes from high-voltage transients. Consequently, this modular separation dramatically streamlines maintenance workflows and simplifies system expansion.

Read more