Configured for power distribution and load management in DeltaV bulk power systems, the Emerson VE5132 (VE5132 Power Supply Redundancy Module) provides direct physical and electrical execution of bulk DC power paralleling. This hardware component enables the consolidation and protection of redundant DC power sources within the cabinet architecture.

Hardware Specifications

Parameter Specification
Model VE5132
Brand Emerson
Origin N/A
Weight 0.91 kg (2.00 lbs)
Dimensions Standard DeltaV Bulk Power Form Factor
Operating Temp Standard Industrial Ambient
Power Consumption Not Specified
Capacity 40 A
Input Voltage Range 12 VDC to 28 VDC

Process Control and Signal Integrity

The module architecture supports the integration of redundant power paths to ensure continuous supply delivery to the system bus. By utilizing parallel diode OR-ing or similar steering circuitry, the module prevents back-feeding from a faulted power supply into the healthy rail, maintaining the stability of the distribution network. The inclusion of conformal coating provides environmental protection against airborne contaminants, ensuring consistent electrical contact and component longevity in diverse industrial atmospheres.

Frequently Asked Questions

Q: Does the VE5132 provide current limiting functionality for individual power supply inputs?

A: The module functions as a redundancy/steering component. Over-current protection remains the responsibility of the individual power supply units or external branch circuit breakers installed upstream of the VE5132.

Q: Is this module capable of being hot-swapped while the system is powered?

A: The VE5132 is designed for insertion into the power distribution assembly. Ensure all redundant power sources are verified for correct voltage potential before installation to avoid current inrush or localized arcing.

Field Installation Guidelines

  • Mounting: Install the module within the designated bulk power distribution rail. Ensure all fasteners are tightened to manufacturer specifications to maintain low-impedance connections for high-current throughput.
  • Grounding: Ensure the power distribution assembly chassis is connected to a verified instrument ground bus. This is necessary for protecting the internal steering diodes and circuitry from transient surge voltages.
  • Wiring: Use appropriately sized cabling capable of handling the 40 A rated current capacity. Ensure cable terminations are clean and free of oxidation to prevent resistive heating at high load levels.
  • Verification: Measure the output voltage at the distribution terminals post-installation to confirm that the redundant power paths are correctly balanced and functioning within the specified 12 VDC to 28 VDC input range.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more
Mastering Wire Identification in Industrial Automation: The Power of Ferrules and Cross-Ferruling

Mastering Wire Identification in Industrial Automation: The Power of Ferrules and Cross-Ferruling

Proper wire labeling forms the cornerstone of reliable control system installation and long-term maintenance. In complex industrial automation environments, technicians terminate thousands of conductor ends inside control panels, marshalling racks, and field junction boxes. Ferrules serve as individual tube-shaped sleeve markers slipped onto conductors before final termination. While technicians historically relied on pre-printed individual letter rings, modern control panel builders utilize automated ferrule printing machines. These thermal-transfer printers generate durable, single-sleeve heat-shrink tags directly matching approved wiring schematics, significantly accelerating cabinet assembly workflows.

Read more