Product Details
Configured for high-density signal distribution in Ovation control networks, the Emerson 5XO0300G02 (5XO0300G02 Analog Output Module) provides direct physical electrical execution for multi-channel voltage command signals. The hardware enables 16-bit resolution output across a range of -10 VDC to +10 VDC to support precise actuator and process control loop requirements.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 5XO0300G02 |
| Brand | Emerson |
| Origin | USA |
| Weight | 0.42 kg |
| Dimensions | 173 mm x 100 mm x 42 mm |
| Operating Temp | -40 deg C to 70 deg C |
| Power Consumption | 24 VDC, 200 mA |
| Number of Channels | 16 |
| Output Range | -10 VDC to +10 VDC |
| Accuracy | 0.1% |
| Update Rate | 250 ms |
Process Instrumentation and Connectivity
The 5XO0300G02 integrates channel-to-channel isolation architecture to prevent common-mode noise propagation between distinct output circuits. This design ensures that electrical disturbances on one loop do not affect the signal integrity of adjacent channels. Furthermore, the module supports standard 4-20 mA HART loop protocol compatibility when utilized with appropriate signal converters, facilitating seamless integration with intelligent field devices within the Ovation ecosystem.
Frequently Asked Questions (FAQ)
Q: Is this module capable of hot-swapping during active process control?
A: Yes, the 5XO0300G02 is designed for hot-swap operations within the Ovation I/O rack, allowing for module replacement without interrupting the backplane communication or de-energizing the entire system.
Q: Does the 250 ms update rate represent the total throughput for all 16 channels?
A: Yes, the specified 250 ms update rate is the standard cycle time for the module to refresh the output registers across all 16 channels simultaneously.
Field Installation Guidelines
- Confirm the 24 VDC power supply capacity is sufficient to handle the 200 mA draw under full-load conditions to prevent voltage sagging.
- Ensure the module is fully seated in the backplane slot; tighten the top and bottom retaining screws to establish a secure ground connection between the chassis and the rack.
- Use shielded cabling for all field output wiring to prevent EMI interference, ensuring the shield drain is terminated at the designated cabinet ground bus.
- Route output signal wiring separately from AC power and high-current relay control lines to maintain signal purity.
- Verify channel-to-channel polarity during termination to avoid short-circuiting the output stages.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.