Product Details

The ABB 560B0R01 1KGT036800R0002, also cataloged as the 560B0R01 Binary Output Module, operates as a dedicated hardware component for switching field discrete control signals within ABB RTU560 platforms.

Hardware Specifications

Parameter Specification
Model 560B0R01 (1KGT036800R0002)
Brand ABB
Origin Germany
Weight 0.202 kg
Dimensions 14 cm x 20.5 cm x 3.8 cm
Operating Temp -25 to +70 deg C
Power Consumption 60 W
Relay Outputs 16 Single-Pole, Normally Open Contacts
Output Grouping 2 Groups of 8 Channels with Common Return
Operating Voltage 24-125 VDC
Max Switching Voltage 150 VDC
Current Capacity Continuous 2 A per Group
Mounting DIN Rail or Panel Mount

Deterministic Network Integration and I/O Density Scaling

The 560B0R01 binary output module establishes a high-density switching interface between the central processing unit and field actuation equipment. Integrated backplane bus communication velocity allows rapid response times for command execution over Profinet and EtherNet/IP deterministic networks without introducing bus contention or signal latency. High channel integration supports scalable I/O density within compact subracks, while onboard memory circuits support firmware flash compatibility across RTU system updates.

Frequently Asked Questions

Q: How are the 16 relay channels isolated and grouped electrically?

A: The 16 single-pole normally open relay outputs are divided into two distinct groups of eight channels, each sharing a common return line for group voltage isolation.

Q: Can the 560B0R01 module be hot-swapped during active system rack operation?

A: Module replacement requires de-energizing the field relay voltages and subrack power supply prior to insertion or removal to prevent electrical arcing and backplane pin damage.

Q: What is the maximum voltage rating for the output relay contacts?

A: The relay contacts support a maximum switching voltage of 150 VDC, with an operating voltage range between 24 VDC and 125 VDC.

Field Installation Guidelines

  • Isolate all external field loop voltages and system subrack power before installing or extracting the module.
  • Observe group current limits by ensuring continuous current across each eight-channel group does not exceed 2 A.
  • Connect external suppression diodes across inductive DC loads to mitigate voltage spikes during relay contact opening.
  • Ensure proper chassis grounding via the DIN rail or panel mounting interface using short, low-impedance connections.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding OpenTelemetry in Industrial Automation: Architecture, Observability, and Operational Benefits

Understanding OpenTelemetry in Industrial Automation: Architecture, Observability, and Operational Benefits

Modern industrial control systems (PLCs, DCS, edge nodes) are rapidly adopting cloud-native architectures, generating vast operational data. OpenTelemetry offers an open-source framework that unifies metrics, logs, and execution traces, enabling standardized observability across industrial automation and IT systems.

Read more
Mastering Functional Safety Terminology in Industrial Automation

Mastering Functional Safety Terminology in Industrial Automation

In modern process control and factory automation, managing operational risk is a top engineering priority. High-speed machinery, high-pressure vessels, and continuous processes present constant hazards to personnel and equipment. Modern plant operations rely heavily on functional safety strategies to mitigate these risks. This guide breaks down the essential functional safety terminology that every control systems engineer should master.

Read more
Understanding Dry Contacts in PLC Wiring: An Industrial Automation Guide

Understanding Dry Contacts in PLC Wiring: An Industrial Automation Guide

Mastering contact switching principles is essential for reliable control panels. Field devices and PLCs interface through dry or wet contacts. This technical guide examines the mechanics of dry contacts, explores their wiring architectures, and evaluates their key advantages in industrial automation.

Read more