PRODUCT SKU : HE693DAC420

PRODUCT TYPE : Analog Output Modules

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE HE693DAC420, also cataloged as the HE693DAC420 Isolated Analog Current Output Module, operates as a dedicated hardware component for converting digital controller commands into 4-20 mA or 0-20 mA current loops within Series 90-30 PLC systems.

Hardware Specifications

Parameter Specification
Model HE693DAC420
Brand GE / GE Fanuc
Origin USA
Operating Temp 0 to 60 deg C
Power Consumption 90 mA @ 5 VDC / 120 mA @ 24 VDC
Number of Channels 4 Channels
Output Range 4-20 mA or 0-20 mA
Resolution 14 bits (13 bits plus sign D/A resolution)
Isolation 1500 VAC (RMS) Channel-to-Channel and Channel-to-Ground
Power Supply External 24 VDC User-Supplied Loop Power
Current Surge on Power-up 250 mA for 10 ms @ 5 VDC / 900 mA for 30 ms @ 24 VDC
Load Impedance Less than or equal to 1.1 kohm @ 24 V Loop Voltage
Maximum Linearity Error 0.10% Full Scale (4-20 mA) / 0.15% Full Scale (0-20 mA)
Relative Humidity 5% to 95%, non-condensing

Deterministic Networks and I/O Density Scaling

The HE693DAC420 module integrates into the Series 90-30 backplane to execute deterministic data updates from the main CPU card. High channel-to-channel and channel-to-ground isolation limits electrical noise propagation across the backplane bus interface, preserving communication velocity across expanded sub-rack configurations. Digital-to-analog processing pathways maintain firmware flash compatibility across standard Series 90-30 rack backplanes while providing stable current outputs under dynamic load resistance variations.

Frequently Asked Questions

Q: Does the HE693DAC420 require an external power source to drive the 4-20 mA loops?

A: Yes. The module relies on an external 24 VDC user-supplied power source to energize the isolated output loops in addition to the 5 VDC backplane logic draw.

Q: Can the HE693DAC420 module be installed or removed from the Series 90-30 rack while backplane power is active?

A: No. Power to the Series 90-30 rack must be completely isolated prior to inserting or removing the module to prevent electrical damage to backplane bus pins and internal D/A converter circuitry.

Field Installation Guidelines

  1. De-energize the Series 90-30 rack power supply and isolate external 24 VDC loop power before mounting or wiring the module.
  2. Slide the HE693DAC420 module firmly into the designated rack slot until the top and bottom retaining clips latch into the backplane baseplate.
  3. Wire the external 24 VDC field power supply to the terminal connector, maintaining correct polarity to support the internal isolation circuitry.
  4. Route 4-20 mA field current loop wiring using twisted-pair shielded cables to prevent inductive noise pickup from adjacent power lines.
  5. Ground all cable shields at a single Earth ground terminal near the panel entrance to avoid establishing ground loop currents.
  6. Verify that maximum loop resistance on each output channel does not exceed 1.1 kohms under 24 VDC operation before powering up the system.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Supervisory Control and Data Acquisition (SCADA) systems form the digital backbone of modern industrial automation. They collect critical field data, transmit signals across vast distances, and empower plant operators with real-time process visibility. Across modern infrastructures, SCADA solutions streamline centralized control and maintain continuous operational uptime.

Read more
Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

In industrial automation, connecting physical hardware with high-level software remains a primary operational challenge. Factories utilize programmable logic controllers (PLCs), distributed control systems (DCS), human-machine interfaces (HMIs), and smart sensors from diverse vendors. These devices often speak different proprietary protocols. Open Platform Communications (OPC) servers solve this interoperability challenge by standardizing how data flows across factory networks.

Read more
Industrial Fiber Optic Cables: Principles, Connectors, and Fusion Splicing Techniques

Industrial Fiber Optic Cables: Principles, Connectors, and Fusion Splicing Techniques

Modern factory automation relies heavily on fiber optic cables for high-speed industrial data transmission. Fiber optic cables transmit light pulses instead of electrical signals, eliminating electromagnetic interference (EMI) risks completely. Each optical strand consists of a high-purity glass core surrounded by a protective cladding layer. The difference in refractive index between core and cladding enables total internal reflection. Protective resin buffers, Kevlar strength members, and rugged outer jackets safeguard delicate glass cores in harsh environments. Consequently, automation engineers prefer fiber backbones for reliable noise-free communication in industrial control systems.

Read more