Product Details
Configured for precision thermal signal acquisition in Ovation distributed control systems, the Emerson 5X00119G03 (5X00119G03 Temperature Module) provides direct physical electrical execution for multi-channel input processing. The module interface handles both thermocouple and Resistance Temperature Detector (RTD) signals, maintaining measurement accuracy across temperature ranges from -200 deg C to 850 deg C, depending on the sensor type connected.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 5X00119G03 |
| Brand | Emerson |
| Origin | Not Specified |
| Weight | Not Specified |
| Dimensions | Standard Ovation Module Factor |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Not Specified |
| Input Channels | Multi-channel (8 or 16) |
| Accuracy | +/- 0.1% of span |
Channel Isolation and Cold Junction Compensation
The 5X00119G03 architecture utilizes channel-to-channel and channel-to-system isolation to suppress common-mode noise and prevent ground loops within the control loop. For thermocouple inputs, the module incorporates cold junction compensation (CJC) circuitry to ensure precise reference temperature tracking. This isolation framework is required to maintain the specified measurement accuracy in industrial environments characterized by high electromagnetic interference, ensuring that validated temperature data is transmitted to the Ovation controller bus without degradation.
Frequently Asked Questions (FAQ)
Q: Does the 5X00119G03 support hot-swapping during normal system operation?
A: Yes, the module supports hot-swap functionality. Ensure that field wiring is secured and the system configuration mode is set to maintenance to avoid signal noise during module insertion or removal.
Q: How is the thermocouple or RTD type selected for each channel?
A: Sensor type selection and channel configuration are performed within the Ovation control system software environment. Ensure the appropriate I/O channel configuration profile is applied to match the connected field hardware.
Field Installation Guidelines
- Inspect the backplane interface slot for pin integrity and absence of debris before installing the module.
- Align the module with the Ovation rack chassis rails and seat it firmly until the mechanical locking lever is fully closed.
- Terminate field signal wiring at the dedicated terminal block, ensuring proper polarity for thermocouples or lead-wire configuration for RTDs.
- Route all sensor cabling using shielded, twisted-pair conductors and ground the shield drain wires to the cabinet common ground bus to maintain noise immunity.
- Verify the operational status through the front-panel LED indicators and confirm that the controller acknowledges the module presence after the hardware installation is complete.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.