Product Details
Configured for optical flame sensor signal analysis and flame detection logic execution in DCS and PLC architectures, the ABB FAU800 (FAU800 Flame Analysis Module) provides direct physical/electrical execution. The module evaluates dynamic flame signals across two independent channels, interfacing directly with ABB flame rods, 4-20 mA sensors, or 0-5 V input signals to control dedicated fault relays within predefined 0.1 to 2.5 second response windows.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FAU800 |
| Brand | ABB |
| Operating Temp | -40 deg C to +70 deg C |
| Power Consumption | 6 W typical |
| Power Supply | 24 VDC (21.6 to 31.2 VDC range), Dual Redundant |
| Signal Input Channels | 2 Independent Channels (Flame rod, 4-20 mA, 0-5 V) |
| Output Relays | Configurable flame fault relay outputs |
| Communication Ports | 2 x PROFIBUS DP (9-pin D-Sub), 2 x Ethernet (RJ45) |
| Isolation Rating | 500 VAC channel-to-channel, 1500 VAC system-to-system |
| System Protocols | PROFIBUS DP-V1 (12 Mbps), Modbus RTU/TCP (100 Mbps) |
Backplane Bus Communication Velocity & I/O Density Scaling
The FAU800 module maintains backplane bus communication velocity and high-speed data throughput via dual PROFIBUS DP interfaces supporting up to 12 Mbps and dual Ethernet ports operating at 100 Mbps. Its twin-channel footprint optimizes cabinet I/O density scaling by consolidating flame sensor signal processing and safety relay output channels into a single chassis slot. Full firmware flash compatibility allows online parameter adjustments and continuous diagnostic status monitoring over Modbus TCP or PROFIBUS network topologies.
Frequently Asked Questions
Q: How is galvanic isolation structured across the FAU800 signal channels?
A: The module provides 500 VAC galvanic isolation between individual signal channels and 1500 VAC isolation between input channels and system logic circuits.
Q: What power redundancy configurations does the FAU800 support?
A: The FAU800 features dual redundant 24 VDC power input terminals, allowing connection to two independent power supplies across the 21.6 VDC to 31.2 VDC operating range.
Q: Can response timing for flame fault detection be configured on the module?
A: Yes. The trip response delay is configurable within a range of 0.1 to 2.5 seconds to match process safety requirement specifications.
Field Installation Guidelines
Follow these technical procedures during panel installation and field cabling:
- Chassis Mounting: Mount the FAU800 module vertically inside the enclosure rail frame, ensuring top and bottom ventilation paths remain unobstructed.
- Ground Bonding: Connect the module chassis ground terminal to the main panel protective earthing (PE) bus using a low-impedance copper strap to minimize high-frequency interference.
- Signal Wiring: Route flame rod, 4-20 mA, and 0-5 V sensor cables in individually shielded twisted pairs. Terminate cable shields at the dedicated chassis earth bar.
- Power & Communication Termination: Wire dual 24 VDC power lines to the redundant input terminals. Secure D-Sub 9 connectors for PROFIBUS or RJ45 Ethernet cables, ensuring retaining screws are locked.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.