PRODUCT SKU : 1746-OX8

PRODUCT TYPE : Digital Relay Output Module

PRODUCT VENDOR : Allen-Bradley


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Description

The Allen-Bradley 1746-OX8 is a digital contact output module for the SLC 500 series. It provides eight normally open relay contact outputs, designed for both AC and DC voltage operation. With individually isolated high-current relay outputs, it is suitable for applications requiring reliable switching of mixed voltage signals.

Technical Specifications

  • Manufacturer Allen-Bradley

  • Category PLCs

  • Product Line SLC 500

  • Part Number 1746-OX8

  • Weight 1.00 lbs (0.45 kg)

  • Module Type Digital contact output module

  • Number of Outputs 8 relay outputs (N.O. contacts)

  • Operating Voltage Range 5–265 VAC or 5–125 VDC

  • Current per Output (120 VAC) 3 A

  • Current per Output (24 VDC) 1.2 A

  • Backplane Current Draw 85–90 mA

  • Step Response 60 ms input, 2.5 ms output

  • Operating Shock Resistance 10 g

  • Application Type Individually isolated, high-current relay switching

Application Scenarios

  • Switching AC and DC loads in mixed-voltage environments

  • Industrial control systems requiring isolated relay outputs

  • Applications needing high-current relay contacts for motor starters, solenoids, or lighting control

FAQ

Q: How many outputs does the 1746-OX8 provide?  A: It provides 8 normally open relay contact outputs.

Q: What is the maximum current per output?  A: 3 A at 120 VAC and 1.2 A at 24 VDC.

Q: Are the outputs isolated?  A: Yes, each relay output is individually isolated for safe operation.

Comparison with Similar Models

  • 1746-OB16: Transistor output module, designed for DC loads.

  • 1746-OW16: Relay output module with wider voltage range and more outputs.

  • 1746-OX8: Compact relay output module with 8 isolated contacts, ideal for high-current switching.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more