Skip to content

What are you looking for?


You may also like

Honeywell 07728000 PLC Digital I/O ModuleHoneywell 07728000 PLC Digital I/O ModuleHoneywell 07728000 PLC Digital I/O Module
Honeywell 07728000 PLC Digital I/O Module
Honeywell 07728000 PLC Digital I/O Module
Honeywell 07728000 PLC Digital I/O Module

Honeywell 07728000 PLC Digital I/O Module


Only 10 left - Selling fast

PRODUCT SKU : 07728000

PRODUCT TYPE : Digital I/O Cards

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for direct digital signal acquisition and command transmission in Experion PKS C300 systems, the Honeywell 07728000 (07728000 PLC Digital I/O Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model 07728000
Brand Honeywell
Origin USA
Weight 0.5 lbs
Dimensions 110 x 80 x 31 mm
Operating Temp -20 deg C to +60 deg C
Power Consumption 24 VDC +/- 10%
I/O Capacity 16 DI / 16 DO
System Compatibility Honeywell Experion PKS C300
Signal Execution Discrete digital input/output

Process Control and DCS Instrumentation Characteristics

The 07728000 digital I/O module integrates into C300 backplane architectures that manage 4-20 mA HART loop protocol diagnostics across hybrid control topologies. Channel-to-channel isolation prevents common-mode noise and ground loops from compromising backplane logic during rapid discrete switching cycles. Integrated cold junction compensation (CJC) processing supports adjacent hybrid temperature monitoring channels within the local enclosure. Connection to the Honeywell Control Bus enables localized digital status reporting and seamless data pass-through to FOUNDATION Fieldbus and Profibus PA network structures.

Frequently Asked Questions

Q: Does the 07728000 module support hot-swapping during runtime?

A: Yes, the C300 series backplane architecture permits hot-swapping this module without removing backplane power or halting host C300 controller execution.

Q: Is external surge suppression required for the 24 VDC digital inputs?

A: Internal transient protection is present, but external surge suppression devices are recommended for long field cable runs exposed to high inductive switching loads.

Q: How is redundant configuration implemented for this module?

A: Redundancy is achieved by installing two 07728000 modules on a paired C300 I/O carrier, where the Honeywell Control Bus manages real-time primary-to-secondary failover based on hardware health diagnostics.

Field Installation Guidelines

  1. Align module backplane pins with the C300 series cabinet carrier slot and seat firmly until the locking tab engages.
  2. Connect the cabinet ground lug directly to the module chassis grounding point to preserve galvanic isolation and discharge static voltage.
  3. Route 24 VDC digital I/O wiring through dedicated wire ducts, keeping field signal leads separated from high-voltage AC lines.
  4. Utilize shielded twisted-pair cabling for extended input/output runs and land the cable shield at the cabinet entry ground bus.
  5. Verify power supply tolerances remain strictly within 24 VDC +/- 10% under full load prior to commissioning field channels.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Industrial automation integrates speech recognition, IIoT protocols, and NLP with PLCs and DCS to streamline operations. By leveraging advanced edge computing, engineers enable real-time, hands-free control—allowing personnel to manage smart factory processes safely away from hazardous equipment.

Read more
Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Industrial automation has evolved from a simple manufacturing tool into the operational backbone of high-risk sectors. Modern mining operations increasingly rely on advanced control systems, programmable logic controllers (PLCs), distributed control systems (DCS), and artificial intelligence to address deep-underground hazards. By replacing manual labor in high-risk zones, factory automation technologies protect personnel while significantly boosting operational throughput.

Read more
Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

System cabinet health checks ensure long-term reliability in industrial automation. Preventative maintenance prevents hardware degradation, communication loss, and unplanned outages in control networks. This guide outlines the standard operating workflow for inspecting PLC and DCS cabinets to maintain peak performance.
Read more