Skip to content

What are you looking for?


You may also like

GE PACSystems RX3i IC694MDL916 16-Point Relay Output ModuleGE PACSystems RX3i IC694MDL916 16-Point Relay Output ModuleGE PACSystems RX3i IC694MDL916 16-Point Relay Output Module
GE PACSystems RX3i IC694MDL916 16-Point Relay Output Module
GE PACSystems RX3i IC694MDL916 16-Point Relay Output Module
GE PACSystems RX3i IC694MDL916 16-Point Relay Output Module

GE PACSystems RX3i IC694MDL916 16-Point Relay Output Module


Only 10 left - Selling fast

PRODUCT SKU : IC694MDL916

PRODUCT TYPE : Relay Output Module

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Description

The IC694MDL916 relay output module from GE Fanuc PACSystems RX3i series provides sixteen individually isolated Form A (Normally Open) relay outputs. Designed for flexible AC/DC switching, it supports a wide voltage range and robust isolation, making it suitable for industrial automation systems requiring reliable relay-based control.

Technical Specifications

  • Manufacturer: GE Fanuc Emerson

  • Product Line: PACSystems RX3i

  • Part Number: IC694MDL916

  • Product Type: Relay Output Module

  • Number of Channels: 16 isolated relay outputs

  • Contact Form: Form A (Normally Open)

  • Operating Voltage Range: 0–125 VDC / 5–250 VAC

  • Nominal Output Voltage: 5/24/125 VDC; 120–240 VAC

  • Output Current per Channel:

    • Minimum: 10 mA

    • Maximum: 4 A (5–250 VAC resistive/general purpose)

    • Maximum: 4 A (5–30 VDC resistive)

    • Maximum: 200 mA (125 VDC resistive)

    • Pilot duty: 2 A per output (5–30 VDC, 5–250 VAC)

    • Lamp load: 2 A per output (5–30 VDC, 5–250 VAC)

  • Switching Current: 4 A maximum

  • Switching Frequency: 20 cycles per minute maximum

  • Response Time: ≤ 10 ms

  • Relay Contact Life: 200,000–1,000,000 operations depending on load type

  • Isolation (Field to Backplane & Frame Ground): 250 VAC continuous; 1500 VAC withstand for 1 minute

  • Isolation (Point-to-Point): Yes

  • Isolation (Group-to-Group): 250 VAC continuous; 1500 VAC withstand for 1 minute

  • Backplane Current Draw: 300 mA at 5 VDC (all outputs ON); 150 mA at 24 VDC relay power (all outputs ON)

  • Terminal Block Options: IC694TBB032 (box-style), IC694TBB132 (extended box-style), IC694TBS032 (spring-style), IC694TBS132 (extended spring-style)

  • Installation: RX3i PACSystems PLC I/O slots

  • Configuration Software: Proficy Machine Edition v5.5 SP2 or later

  • Weight: 0.69 lbs (0.31 kg)

  • Lifecycle Status: Active

Application Scenarios

  • Industrial automation systems requiring AC/DC relay switching

  • Applications needing isolated outputs for safety and reliability

  • Environments where pilot duty and lamp load switching are common

FAQ

Q: How many relay outputs does this module provide?  A: 16 individually isolated Form A (Normally Open) relay outputs.

Q: What voltage ranges are supported?  A: 0–125 VDC and 5–250 VAC.

Q: What is the maximum switching current?  A: 4 Amps for resistive loads at 5–250 VAC or 5–30 VDC.

Q: What is the expected relay contact life?  A: Between 200,000 and 1,000,000 operations depending on voltage and load type.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Modern manufacturing relies heavily on automated control systems to maximize throughput and maintain product quality. However, unplanned downtime in industrial automation can cost facility operators thousands of dollars per hour. Understanding how programmable logic controllers (PLCs), distributed control systems (DCS), and field instrumentation fail empowers engineering teams to implement robust preventive maintenance strategies.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

Implementing robust protection in hazardous industrial environments represents a fundamental safety requirement in factory automation. Process facilities often handle volatile gases, dusts, and chemical agents that pose significant combustion risks. Consequently, control system engineers must deploy energy-limiting interfaces to isolate safe-area control cabinets from hazardous-area field instrumentation. This article examines the function, selection, and electrical principles of intrinsic safety barriers within modern PLC and DCS networks.

Read more