Product Details

Configured for non-contact displacement measurement in rotating machinery monitoring networks, the Emerson epro PR6424/013-140 CON021 (PR6424/013-140) Eddy Current Proximitor System provides direct physical execution of dynamic and static signal conversion for axial and radial shaft monitoring.

Hardware Specifications

Parameter Specification
Model PR6424/013-140 CON021
Brand Emerson epro
Origin Not Specified
Weight 0.32 kg (Combined system)
Dimensions M18x1.5 (Sensor) / DIN-rail mount (Converter)
Operating Temp -30 deg C to +100 deg C (Converter)
Power Consumption 23 VDC to 32 VDC

Mechanical Monitoring and TSI Integration

The PR6424/013-140 utilizes electromagnetic induction to measure the distance relative to a rotating metallic shaft. Achieving accurate rotor dynamics data necessitates precise eddy-current probe scaling to ensure the output voltage reflects true mechanical displacement at a sensitivity of 4 V/mm. During installation, users must verify gap voltage validation, maintaining targets near -10 VDC to ensure operation within the linear range of the probe's characteristic curve. Furthermore, to preserve high-fidelity waveform capture, the system requires effective cross-talk suppression by ensuring proper routing and shielding of the 10 m interconnecting coaxial cables, preventing common-mode noise from influencing the perceived shaft position or vibration frequency.

Frequently Asked Questions

Q: Can the 10 m cable length of the PR6424/013-140 be field-shortened?

A: No. The system is factory-calibrated as a complete signal chain. Altering the coaxial cable length changes the system impedance and resonant frequency, which introduces significant measurement errors.

Q: Is the system sensitive to power supply fluctuations?

A: The CON021 operates within a -23 VDC to -32 VDC supply range. Voltage levels outside this window may cause signal drift or non-linear output response, impacting the reliability of the protective trip logic in connected monitoring systems.

Field Installation Guidelines

  1. Probe Gap Setting: Establish the initial gap between the probe tip and the shaft surface using a calibrated feeler gauge. Target the mid-point of the linear measurement range to allow for shaft movement in both directions.
  2. Mounting Integrity: Secure the probe within a rigid, vibration-isolated bracket. Any flexure in the mounting assembly will be perceived by the sensor as shaft vibration, resulting in erroneous condition monitoring data.
  3. Cable Routing: Route coaxial cables away from high-current power lines and variable frequency drive (VFD) outputs. Use shielded conduits to prevent electromagnetic interference (EMI) from inducing noise into the high-impedance signal path.
  4. Connector Care: Inspect the Lemo-plug connections for contaminants or moisture. Ensure the interface is clean and dry to prevent leakage paths that cause signal attenuation and gap voltage drift.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more