Product Details

Configured for high-precision data acquisition in M1 automation platforms, the Bachmann AI204/2 (AI204/2 Analog Input Module) provides direct physical/electrical execution of two-channel voltage measurement with sub-millisecond sampling capabilities.

Hardware Specifications

Parameter Specification
Model AI204/2
Brand Bachmann
Origin Austria
Weight 0.28 kg
Dimensions 102 mm x 12 mm x 130 mm
Operating Temp 0 deg C to 60 deg C
Power Consumption 2.5 W
Input Channels 2
Input Range ±10 V
Resolution 16-bit
Sampling Time 20 μs

Profinet / EtherNet/IP Deterministic Networks

The AI204/2 integrates into the M1 backplane to facilitate deterministic network connectivity between field sensors and the controller. The module's architecture is optimized for backplane bus communication velocity, ensuring that high-speed data streams—sampled at 20 μs—are processed without jitter. I/O density scaling is supported through the module's small form factor, allowing for multiple high-speed analog inputs to be deployed within a single rack. Firmware flash compatibility is maintained, ensuring that digital averaging algorithms and the signal processing stack remain compliant with the latest controller firmware revisions.

Frequently Asked Questions

Q: Can the channels be operated as non-isolated inputs?

A: The AI204/2 features single isolation for each channel, providing protection against ground loops between connected analog sources. Ensure all source commons are verified against the module's reference potential.

Q: How does the digital averaging function affect the output latency?

A: Digital averaging improves the signal-to-noise ratio by processing multiple samples; however, this creates a trade-off with group delay. Users should tune the averaging depth to match the process loop bandwidth requirements.

Q: Is the ±10 V range fixed or software-scalable?

A: The input stage is calibrated for a ±10 V range at 16-bit resolution. Scaling and normalization are performed in the software application layer, allowing for the mapping of raw counts to engineering units.

Field Installation Guidelines

  1. Shielding: Connect cable shields to the cabinet functional earth (FE) using low-impedance clamps as close to the module as possible to maximize noise immunity.
  2. Signal Integrity: Given the 20 μs sampling time, maintain minimal wire lengths and use twisted-pair cabling to minimize susceptibility to radiated electromagnetic interference.
  3. Common Mode: Although the module is isolated, ensure that the common-mode voltage between the two channels does not exceed the specified safety limits defined for the input stage.
  4. Connector Seating: Ensure the terminal block is securely locked into the module housing to prevent intermittent contact resistance, which can cause significant measurement errors in high-precision (0.005%) circuits.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redefining Control Systems: The Rise of Flexible I/O Modules in Industrial Automation

Redefining Control Systems: The Rise of Flexible I/O Modules in Industrial Automation

Conventional input-output architectures often limit engineering agility and inflate long-term inventory costs. Today, Flexible Input/Output Modules (FIOM) are transforming how control system engineers design, commission, and maintain automation infrastructure. By allowing individual channel software configuration, FIOM technology bridges the gap between rigid hardware design and dynamic plant requirements.

Read more
Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Supervisory Control and Data Acquisition (SCADA) systems form the digital backbone of modern industrial automation. They collect critical field data, transmit signals across vast distances, and empower plant operators with real-time process visibility. Across modern infrastructures, SCADA solutions streamline centralized control and maintain continuous operational uptime.

Read more
Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

In industrial automation, connecting physical hardware with high-level software remains a primary operational challenge. Factories utilize programmable logic controllers (PLCs), distributed control systems (DCS), human-machine interfaces (HMIs), and smart sensors from diverse vendors. These devices often speak different proprietary protocols. Open Platform Communications (OPC) servers solve this interoperability challenge by standardizing how data flows across factory networks.

Read more