Product Details
The GE IS200JPDMG1ACC, also cataloged as the IS200JPDMG1 Power Distribution Card, operates as a dedicated hardware component for localized power distribution and individual circuit protection to I/O packs within GE Mark VIe Control Systems.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IS200JPDMG1ACC |
| Brand | GE / General Electric |
| Origin | USA |
| Dimensions | Standard Mark VIe DIN-Rail PCB Mount |
| Operating Temp | -30 to +65 deg C |
| Power Consumption | Passive Power Distribution / Circuit Protected |
| Primary Power Input | 125 VDC Nominal Battery Source or Converted 120/240 VAC |
| Daisy-Chain Port Type | J1 and J1X Daisy-Chain Bus Connectors |
| Hazardous Location Certification | Class 1 Division 2 / ATEX Zone 2 Compliant |
| Protection Components | 24 Varistors and 24 Two-Position Plugs (3 Rows of 8) |
Backplane Bus Communication Velocity and Firmware Flash Compatibility
The IS200JPDMG1ACC card routes conditioned DC power directly to individual rack-mounted I/O packs, isolating transient overvoltage spikes through 24 onboard metal oxide varistors. By offloading power management and short-circuit protection execution from the central controller racks, the board stabilizes local DC supply voltages and prevents power-fault propagation that could disrupt backplane bus communication velocity across the Mark VIe control architecture. The passive distribution topology operates independently of digital logic, ensuring continuous firmware flash compatibility across all Mark VIe control system software updates and module replacements.
Frequently Asked Questions
Q: What are the current limitations when daisy-chaining multiple IS200JPDMG1ACC boards via J1 and J1X connectors?
A: The total current draw of all daisy-chained boards must not exceed the maximum current rating of the primary J1 input plug on the first JPDH board in the chain.
Q: How are individual I/O pack power lines protected against electrical faults on the IS200JPDMG1ACC?
A: The board incorporates 24 onboard varistors alongside 24 two-position plug terminals, arranged in three rows of eight, to provide discrete overvoltage protection and localized branch fusing.
Field Installation Guidelines
- Disconnect the main 125 VDC battery power feed or AC conversion source before touching input power connections.
- Verify Class 1 Division 2 or ATEX Zone 2 hazardous location compliance before opening protective enclosures in classified areas.
- Secure the IS200JPDMG1ACC card onto the enclosure mounting base using proper grounding hardware to ensure varistor surge suppression pathways to earth ground.
- Wire input power leads to the main J1 terminal, verifying that downstream daisy-chained connections via J1X remain within total input plug current limits.
- Connect output power leads to the two-position plugs, ensuring shield lines are grounded at the system common point.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.