  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for signal termination and scaling in Mark V control systems, the GE DS200TBQCG1A (DS200TBQC Analog Input/Output Termination Module) provides direct physical execution of LVDT/R and 4-20 mA signal routing between field devices and the TCQA processing core.

Hardware Specifications

Parameter Specification
Model DS200TBQCG1A
Brand General Electric
Origin USA
Operating Temp Standard industrial range
Power Consumption Not specified
Terminal Blocks 2 blocks (TB1, TB2), 83 terminals each (166 total)
Connectors 3 x 40-pin, 3 x 34-pin

Industrial Control and Firmware Flash Compatibility

The DS200TBQCG1A manages critical analog data exchange between the TCQA boards located in the R1, R2, and R3 cores. Deterministic signal handling is supported by hardware-defined pathways: the JBR connector facilitates bi-directional 4-20 mA loop communication, while the JFR connector handles LVDT/R position input processing. The board architecture allows for I/O density scaling through 166 discrete terminal points. Firmware flash compatibility is not applicable, as signal conditioning logic is executed via physical hardware jumpers that determine output current ranges (20 mA or 200 mA maximum). This hardwired configuration ensures that scaling parameters remain fixed regardless of processor state, providing consistent feedback to the control core.

Frequently Asked Questions

Q: Can the output current range be modified through system software?

A: No. Output current range selection (20 mA or 200 mA maximum) is managed exclusively by physical hardware jumpers on the TBQC board. These must be verified against the specific field device requirements prior to commissioning.

Q: What is the purpose of the 15 onboard jumpers?

A: The 15 jumpers are provided for the manual configuration of circuit paths and signal scaling options. Most settings are factory-configured for specific core-to-TCQA signal requirements and should not be modified without explicit reference to the control system schematic.

Field Installation Guidelines

  1. De-energize the Mark V R1, R2, and R3 cores entirely before accessing the TBQC board to prevent damage to the TCQA interface or shorting of the 4-20 mA analog loops.
  2. Verify all field wiring at the TB1 and TB2 terminal blocks; ensure that high-level analog signals are shielded and that the shields are bonded to the designated chassis ground to prevent electromagnetic interference.
  3. Handle the module by the edges and use electrostatic discharge (ESD) mitigation techniques to protect the high-density connector interfaces.
  4. Ensure all ribbon cables (connected to JBR, JFR) are fully seated and locked into their headers to guarantee reliable signal transmission between the termination module and the processing core.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Instrumentation Control Systems in Modern Industrial Automation

Understanding Instrumentation Control Systems in Modern Industrial Automation

An instrumentation control system (ICS) serves as the central nervous system of modern manufacturing plants and processing facilities. Engineers classify these setups as Electrical, Electronic, or Programmable Electronic Systems (E/E/PES). In practice, an ICS bridges the physical world of industrial machinery with digital decision-making tools. Therefore, understanding its architecture is essential for anyone working in factory automation, process control, or plant safety.

Read more
Mastering Electrical Grounding Fundamentals in Industrial Automation and Control Systems

Mastering Electrical Grounding Fundamentals in Industrial Automation and Control Systems

Electrical grounding is a complex engineering discipline. It requires deep knowledge of soil composition and conductor materials. National Electrical Code (NEC) Article 250 outlines these requirements clearly. Many engineers confuse grounding, earthing, and bonding. Grounding connects circuits to a common reference point. Earthing specifically links equipment directly to the planet. Bonding permanently joins metallic parts to ensure electrical continuity.

Read more
Architectural Blueprint of Industrial Automation and Control Systems (IACS): Standards, Safety, and Remote Operations

Architectural Blueprint of Industrial Automation and Control Systems (IACS): Standards, Safety, and Remote Operations

According to IEC 62443, Industrial Automation and Control Systems (IACS) integrate personnel, hardware, and software. These components collectively influence the safety and reliability of any industrial process. Modern control systems allow extensive remote monitoring and operation. However, enabling remote capabilities introduces complex cybersecurity challenges. Therefore, facility operators must evaluate system functions carefully before expanding connectivity.

Read more