Skip to content

What are you looking for?


You may also like

Emerson VE4021 M-series Zone 2 Remote I/O UnitEmerson VE4021 M-series Zone 2 Remote I/O UnitEmerson VE4021 M-series Zone 2 Remote I/O Unit
Emerson VE4021 M-series Zone 2 Remote I/O Unit
Emerson VE4021 M-series Zone 2 Remote I/O Unit
Emerson VE4021 M-series Zone 2 Remote I/O Unit

Emerson VE4021 M-series Zone 2 Remote I/O Unit


Only 10 left - Selling fast

PRODUCT SKU : VE4021

PRODUCT TYPE : Remote I/O Units

PRODUCT VENDOR : EMERSON


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for distributed process control in DeltaV networks, the Emerson VE4021 (VE4021 Remote I/O Unit) provides direct physical and electrical execution of remote signal aggregation. This hardware component manages I/O data traffic and communication between field-mounted I/O cards and the primary controller across high-speed Ethernet links, enabling scalable I/O distribution in Zone 2 hazardous areas.

Hardware Specifications

Parameter Specification
Model VE4021
Brand Emerson
Origin USA / Germany
Weight 0.2 kg
Dimensions 10 cm × 6 cm × 2 cm
Operating Temp Standard Industrial Ambient
Power Consumption System Power Supply Input
I/O Capacity Up to 8 simplex I/O cards per carrier
Comm Ports Dual 10/100 MB Ethernet (RIU2)

Process Control and Communication Connectivity

The module architecture supports deterministic I/O data exchange through dual 10/100 MB Ethernet ports, providing redundancy for primary and secondary communication paths. Each unit facilitates full HART data passthrough, allowing direct integration with AMS Device Manager for remote asset management and diagnostics. The unit supports shared I/O targeting, enabling up to 4 controllers to access card-level data, with a system-wide capacity of 16 Remote I/O Units per controller and up to 300 units across the entire network.

Frequently Asked Questions

Q: Is the VE4021 RIU2 compatible with older DeltaV system versions?

A: The next-generation RIU2 is drop-in compatible with systems running DeltaV version 13.3.1 and later. Ensure that the existing firmware and communication configuration are updated to support the RIU2 dual-port functionality.

Q: Can the Remote I/O Unit manage redundant controller connections?

A: The architecture allows each Remote I/O Unit to be mapped to as many as 4 controllers. Controllers can be configured for redundant operations, and cards are assigned individually to satisfy specific process control loops.

Field Installation Guidelines

  • Mounting: Install the VE4021 on the dedicated 8-wide I/O carrier. Ensure the module is properly latched to the carrier rail to maintain mechanical stability and reliable backplane bus contact.
  • Grounding: Verify that the I/O carrier is bonded to a low-impedance cabinet earth ground. Proper chassis grounding is necessary to protect communication circuitry from surge voltages and electrostatic discharge.
  • Wiring: Route Ethernet communication cables through shielded conduits or segregated trays to prevent crosstalk and radiated electromagnetic interference. Ensure that all Ethernet terminations meet TIA/EIA standards for industrial high-speed links.
  • Verification: Prior to commissioning, confirm the network IP addressing and communication link status via the DeltaV diagnostics interface. Verify that the RIU2 dual-port redundancy is active by observing the link-state LEDs.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Comprehensive Guide to Servo Motor Drive Control Techniques in Industrial Automation

Comprehensive Guide to Servo Motor Drive Control Techniques in Industrial Automation

Precision motion control systems drive high-throughput manufacturing across modern industrial automation environments. Unlike standard induction motors running on basic variable frequency drives, servo motor systems deliver sub-millimeter positioning accuracy and fast dynamic response.

Read more
Industrial PLC Communication Protocols: A Comprehensive Engineering Guide

Industrial PLC Communication Protocols: A Comprehensive Engineering Guide

Modern factory automation relies heavily on industrial communication protocols to connect field instruments, controllers, and enterprise networks. Beyond traditional hardwired I/O, robust communication networks allow programmable logic controllers (PLCs) to exchange telemetry, diagnostic data, and control commands efficiently across complex architectures.

Read more
Understanding PLC Digital Output Types: Relay, Transistor, and Triac Explained

Understanding PLC Digital Output Types: Relay, Transistor, and Triac Explained

Programmable Logic Controllers (PLCs) form the backbone of modern industrial automation systems. They interface directly with field devices such as solenoid valves, indicator lights, motor starters, and interposing relays. Selecting the correct digital output module ensures high system availability and long hardware service life.

Read more