Product Overview

The Yokogawa ALP111-S00 functions as a high-performance PROFIBUS-DP Communication Module designed for the CENTUM series control systems. It establishes a robust digital link between the Distributed Control System (DCS) and field devices such as motor starters, actuators, and remote I/O. We offer this module as 100% Brand New and Original, ensuring seamless integration and factory-standard data throughput for your automated processes.

Part Number Breakdown

The ALP111 series follows Yokogawa's standard configuration logic:

  • ALP111: PROFIBUS-DP Communication Module (Standard 1-Port)

  • -S: Standard Type interface

  • 0: Always 0 (Standard specification)

  • 0: Basic type without additional specialized options

Technical Specifications

The ALP111-S00 provides a high-speed, isolated communication path for industrial fieldbus applications.

Feature Specification Details
Communication Protocol PROFIBUS-DP
Physical Interface EIA-RS-485-compliant
Signal Isolation Fully Isolated (Protects system electronics)
Transmission Speed Auto-detects 9600 bps to 12 Mbps
Communication Port One D-sub 9-pin (female)
Maintenance Port One D-sub 9-pin (male), RS-232C interface
Max Segment Distance 1.2 km (at 9600 bps)
Current Consumption 0.7 A (Maximum)
Shipping Weight 2.0 Kg

Engineering Advantages

  • Superior Signal Isolation: The ALP111-S00 features isolated circuitry between the communication bus and the internal system logic. This barrier blocks high-voltage surges and ground loops common in industrial environments, preventing damage to the central control station.

  • Flexible Speed Adaptation: The module automatically synchronizes with the bus speed, supporting a wide range from 9600 bps up to 12 Mbps. This flexibility allows for long-distance segments at lower speeds or high-speed cyclical data exchange for time-critical control loops.

  • Shielded Transmission Route: Designed for shielded twisted-pair cabling, the module effectively rejects electromagnetic interference (EMI). This ensures signal integrity even when routing cables through trays containing high-power motor leads.

  • Integrated Diagnostics: The dedicated RS-232C maintenance port allows for direct local configuration and troubleshooting. Engineers can verify bus status and device addressing without interrupting the primary PROFIBUS traffic.

FAQs

Does the ALP111-S00 support redundancy?

Yes. In a CENTUM VP or CS 3000 environment, you can install a pair of ALP111 modules in a dual-redundant configuration. This setup ensures that if one module fails, the backup unit takes over communication instantly to prevent process downtime.

What type of connector do I need for the PROFIBUS-DP port?

The module utilizes a standard D-sub 9-pin female connector. You should use a high-quality PROFIBUS-specific plug (typically with a built-in termination resistor) to ensure reliable RS-485 signal levels.

How does the transmission distance change with speed?

While the module reaches up to 1.2 km at 9600 bps, the maximum distance decreases as speed increases. For instance, at 12 Mbps, the segment length typically limits to 100 meters without repeaters. Always consult your network design plan for specific cable limitations.

Is this ALP111-S00 unit factory sealed?

Absolutely. We supply only 100% Brand New Yokogawa hardware. Every module ships in its original factory anti-static packaging, complete with the official manufacturer serial number to guarantee authenticity and a full service life.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Modern manufacturing relies heavily on automated control systems to maximize throughput and maintain product quality. However, unplanned downtime in industrial automation can cost facility operators thousands of dollars per hour. Understanding how programmable logic controllers (PLCs), distributed control systems (DCS), and field instrumentation fail empowers engineering teams to implement robust preventive maintenance strategies.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

Implementing robust protection in hazardous industrial environments represents a fundamental safety requirement in factory automation. Process facilities often handle volatile gases, dusts, and chemical agents that pose significant combustion risks. Consequently, control system engineers must deploy energy-limiting interfaces to isolate safe-area control cabinets from hazardous-area field instrumentation. This article examines the function, selection, and electrical principles of intrinsic safety barriers within modern PLC and DCS networks.

Read more