Product Overview

The Allen Bradley 1734-IV8 functions as a high-density digital input module within the POINT I/O™ family. This module provides eight sourcing-type input points, allowing for seamless integration of 24V DC field devices such as proximity sensors, limit switches, and photoelectric eyes. Its ultra-compact, modular design minimizes panel space while providing granular I/O expansion for distributed control architectures. We supply this unit in 100% Brand New and Original condition, ensuring maximum signal integrity and backplane compatibility for your Logix-based control systems.

Technical Specifications

The 1734-IV8 delivers precise digital signal detection across the following parameters:

Feature Specification
Manufacturer Allen Bradley (Rockwell Automation)
Product Line POINT I/O (1734)
Number of Inputs 8 Points
Input Type DC Digital (Sourcing)
Rated Input Voltage 24V DC
Input Voltage Range 10–28.8V DC
POINTbus Current 75 mA
Isolation Voltage 50V (Continuous)
Status Indicators 8 Yellow I/O Status LEDs; 1 Green/Red Module Status
Mounting DIN Rail (Horizontal or Vertical)
Weight 0.06 lbs (0.03 kg)

Engineering Advantages

The 1734-IV8 addresses critical spatial and diagnostic challenges in modern automation:

  • High-Density Footprint: The "Point" architecture allows for 8 discrete inputs in a housing less than 13mm wide. This compact scale enables significant I/O expansion in small junction boxes or crowded control cabinets where traditional rack-based I/O is physically impossible.

  • Sourcing Input Configuration: This module utilizes a sourcing (PNP-compatible) input structure. It provides a common ground for the field devices, simplifying the wiring of 3-wire PNP sensors and reducing the need for additional terminal blocks.

  • Real-Time Visual Diagnostics: Integrated LED indicators provide instantaneous feedback for each of the 8 points. Technicians can identify faulty field devices or broken wires at a glance without utilizing a programming terminal, significantly reducing Mean Time to Repair (MTTR).

  • Flexible Mounting and Assembly: The module snaps onto a 1734-TB or 1734-TBS terminal base. This "Removal and Insertion Under Power" (RIUP) capability allows for module replacement without disturbing the field wiring or interrupting the power to other modules on the same DIN rail.

FAQs

  • What is the difference between the 1734-IB8 and the 1734-IV8?

    The 1734-IB8 is a sinking input module (requires sourcing sensors), whereas the 1734-IV8 is a sourcing input module (requires sinking sensors). Always verify the output type of your field devices (PNP vs. NPN) before selecting the module to ensure electrical compatibility.

  • Which terminal base does the 1734-IV8 require?

    This module installs onto a 1734-TB, 1734-TBS, or 1734-TOP terminal base. The base provides the connection points for field wiring and secures the module to the DIN rail.

  • Can I replace this module while the system is powered?

    Yes. The POINT I/O system supports RIUP (Removal and Insertion Under Power). You can remove and replace the 1734-IV8 module while the rest of the I/O system remains operational, provided you follow standard industrial safety procedures.

  • Is this a genuine, factory-sealed Allen Bradley unit?

    We guarantee the unit is 100% Brand New and Original. Every 1734-IV8 ships in its original factory packaging with the authentic UPC (612598309832) and Rockwell Automation quality inspection seals intact.

 

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Batch vs Continuous Processing in Industrial Automation: Architectural Strategies for Control Engineers

Batch vs Continuous Processing in Industrial Automation: Architectural Strategies for Control Engineers

Selecting the proper control architecture remains a pivotal decision when designing industrial automation systems. Automation engineers must evaluate whether a batch or continuous process model best fits their production requirements. This fundamental choice influences PLC and DCS programming, hardware redundancy, sensor selection, and overall factory automation layouts.

Read more
Demystifying Signal Isolators: Operating Principles, Architectural Types, and Industrial Applications

Demystifying Signal Isolators: Operating Principles, Architectural Types, and Industrial Applications

Industrial automation systems rely on pristine analog signal transmission across complex control loops. Instrument technicians and system integrators frequently deploy signal isolators to maintain signal integrity between field sensors and control platforms. Eliminating electrical noise, ground loops, and high-voltage transients protects delicate PLC, DCS, and SCADA input channels from permanent damage.

Read more
Demystifying Industrial Control Systems: Comparing PLC, DCS, RTU, SCADA, and PAC

Demystifying Industrial Control Systems: Comparing PLC, DCS, RTU, SCADA, and PAC

Modern factory automation relies on distinct control architectures to manage complex process environments efficiently. Control engineers often evaluate PLC, DCS, RTU, SCADA, and PAC platforms when designing industrial infrastructure. Understanding the functional boundaries of each technology ensures optimal system performance, high availability, and long-term cost efficiency.

Read more