PRODUCT SKU : 5X00500G01

PRODUCT TYPE : Digital Output Modules

PRODUCT VENDOR : EMERSON


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for discrete control signal execution in Ovation distributed control systems, the Emerson 5X00500G01 (5X00500G01 Digital Output Module) provides direct physical execution of 32-channel current-sourcing outputs.

Hardware Specifications

Parameter Specification
Model 5X00500G01
Brand Emerson
Origin USA
Weight Standard Ovation I/O weight
Dimensions Standard Ovation I/O form factor
Operating Temp Industrial standard range
Power Consumption Cabinet auxiliary 24 VDC
Output Count 32 Current Sourcing Channels
Output Current 500 mA per channel (2 A total limit)

Galvanic Isolation

The 5X00500G01 utilizes galvanic isolation of +/- 1000 VDC between field-side and logic-side circuits to maintain system integrity. This isolation prevents transient spikes or ground-side perturbations in field wiring from impacting the internal backplane logic. The module controls external loads by switching positive 24 VDC power sourced from cabinet auxiliary supplies. Field power presence detection is integrated to monitor supply availability, and the module supports stored electronic ID information for automated recognition of module type, group, serial number, and revision.

Frequently Asked Questions

Q: Does the module support hot-swap capability under load?

A: Yes, the 5X00500G01 is designed for hot-swap operations, permitting module replacement without initiating a full system shutdown. Ensure that field wiring is disconnected or de-energized to prevent short circuits during the physical extraction of the module from the chassis.

Q: What is the maximum current capacity per output channel versus the total module limit?

A: Each individual channel is capable of sourcing 500 mA; however, the cumulative current across all 32 channels must not exceed the module-wide total current limit of 2 A.

Field Installation Guidelines

  1. Ensure the chassis slot is clear of obstructions and align the module with the backplane guide rails prior to insertion.
  2. Verify that the auxiliary 24 VDC power supply connected to the cabinet is within the rated operating limits of the module.
  3. Terminate field output cabling to the appropriate terminal block, ensuring each connection is torqued according to specification to prevent high-resistance contact points.
  4. Route output wiring in dedicated low-voltage channels, maintaining separation from high-voltage AC cabling to prevent inductive coupling.
  5. Confirm that the field power presence indicator is active post-installation and utilize the Ovation workstation software to verify channel-level logic status and fault diagnostic registers.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Industrial automation integrates speech recognition, IIoT protocols, and NLP with PLCs and DCS to streamline operations. By leveraging advanced edge computing, engineers enable real-time, hands-free control—allowing personnel to manage smart factory processes safely away from hazardous equipment.

Read more
Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Industrial automation has evolved from a simple manufacturing tool into the operational backbone of high-risk sectors. Modern mining operations increasingly rely on advanced control systems, programmable logic controllers (PLCs), distributed control systems (DCS), and artificial intelligence to address deep-underground hazards. By replacing manual labor in high-risk zones, factory automation technologies protect personnel while significantly boosting operational throughput.

Read more
Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

System cabinet health checks ensure long-term reliability in industrial automation. Preventative maintenance prevents hardware degradation, communication loss, and unplanned outages in control networks. This guide outlines the standard operating workflow for inspecting PLC and DCS cabinets to maintain peak performance.
Read more