Product Overview

The Allen Bradley 1791-OA16 provides a high-density, self-contained solution for distributed digital control. As a primary member of the 1791 Block I/O family, this module eliminates the need for a separate rack and power supply, interfacing directly with PLC-2, PLC-3, and PLC-5 processors. We supply this unit as 100% Brand New original stock, offering a vital lifecycle extension for legacy automation systems that require precise 120VAC load switching.

Technical Specifications

The 1791-OA16 utilizes a dual-group architecture to manage 16 independent AC outputs.

Parameter Specification
Manufacturer Allen Bradley (Rockwell Automation)
Output Type Digital AC Output
Number of Outputs 16 (Two groups of 8)
Nominal Voltage 120 VAC
Operating Voltage Range 20–132 VAC
Max. On-State Current 500 mA per output (at 120V)
Minimum Load Current 50 mA per output
Surge Current 10 A for 50 ms (repeatable every 2 sec)
On-State Voltage Drop 1.5V peak @ 300mA
OFF State Leakage 3 mA (max)
External Power Requirement 85–132 VAC

Engineering Advantages

  • Self-Contained Efficiency: The 1791-OA16 integrates the I/O adapter, power supply, and terminal block into a single footprint. This "Block" design saves significant DIN rail space and reduces the total cost of installation by removing the requirement for an I/O chassis.

  • High Surge Handling: Industrial inductive loads like solenoids and motor starters often generate high inrush currents. The 1791-OA16 handles 10A surges for up to 50ms, protecting the internal circuitry while ensuring successful activation of heavy-duty field devices.

  • Flexible Mounting Geometry: Engineers can mount the block either vertically or horizontally. This flexibility allows the module to fit into shallow junction boxes or narrow side-panels where traditional rack-mounted I/O cannot go.

  • Robust Timing for Synchronized Control: The module achieves a fast turn-on delay of 1.0 ms. For de-energizing, it follows zero-cross principles (8.3ms @ 60Hz), which reduces electrical noise and extends the mechanical life of connected AC actuators.

FAQs

  • Can the 1791-OA16 replace a standard 1771 rack-mounted AC output module?

    Functionally, yes. While the 1771 series requires a chassis, the 1791-OA16 performs the same 120VAC output switching but as a standalone block. It communicates via the same Remote I/O (RIO) link, making it an excellent choice for adding points to an existing PLC-5 system without adding a new rack.

  • What should I consider regarding the 3mA leakage current?

    Small AC loads, such as high-impedance relays or LED indicators, may remain "ON" due to the 3mA leakage current even when the output is technically "OFF." If using very low-current field devices, install a bleed resistor (load resistor) across the output to ensure the device drops below its holding current.

  • Is the external 85-132V AC power required for the logic side or the load side?

    The external power source drives the internal logic and the communication circuitry of the block. You must provide a stable 120VAC source to the power terminals to maintain the RIO link, independent of the voltage applied to the output loads.

  • Does this module support individual channel isolation?

    The 16 outputs are organized into two groups of eight. While the groups are isolated from each other, the eight channels within a single group share a common return. Ensure your wiring plan accounts for this shared common to avoid accidental backfeeding.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying Programmable Logic Controllers: Comprehensive Guide to PLC Classification and Selection in Industrial Automation

Demystifying Programmable Logic Controllers: Comprehensive Guide to PLC Classification and Selection in Industrial Automation

Modern industrial automation heavily relies on Programmable Logic Controllers (PLCs) to drive factory floor efficiency. Over my 15 years as an industrial automation expert working with DCS, TSI, and control systems, I have seen PLCs evolve into the central nervous system of modern manufacturing. Selecting the right controller requires a deep understanding of PLC types based on physical size, hardware architecture, and power supply configurations.

Read more
Comprehensive Guide to PLC Types in Modern Industrial Automation

Comprehensive Guide to PLC Types in Modern Industrial Automation

Modern industrial automation relies on programmable logic controllers to govern critical factory operations. System integrators classify PLCs based on scale, hardware architecture, and power supply design. Understanding these core categories enables automation engineers to select the right control system architecture. Consequently, proper hardware selection optimizes performance while minimizing long-term operational costs.

Read more
Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Modern control systems rely heavily on seamless interprocess communication to exchange operational data between software programs. Microsoft first introduced the Dynamic Data Exchange (DDE) protocol in 1987 to enable real-time data sharing. In factory automation, DDE served as an early bridge between control software and Windows desktop applications. Therefore, understanding DDE mechanics provides crucial insights into how legacy industrial networks established software-level connectivity.

Read more