Product Overview

The 1756-PB50 serves as a high-capacity DC power supply specifically engineered for the Allen-Bradley ControlLogix platform. It converts a nominal 24V DC input into the multiple backplane voltages required by processors, I/O modules, and communication adapters within a 1756 chassis. This module provides the necessary current for high-density configurations, ensuring stable logic-side performance across the entire backplane. We supply this unit as 100% Brand New and factory-original, guaranteeing peak electrical efficiency and system integrity.

Technical Specifications

The 1756-PB50 utilizes a robust switching architecture to maintain stable outputs even during input voltage fluctuations.

Feature Specification
Input Voltage (Nominal) 24V DC
Input Voltage Range 18–32V DC
Backplane Current Capacity (5.1V) 8A @ 50 °C / 6A @ 60 °C
Backplane Current Capacity (24V) 2.5A @ 50 °C / 2.0A @ 60 °C
Max Inrush Current 30 Amps
Isolation Voltage 250V Continuous
Hold Up Time 30ms @ 60W / 40ms @ 50W
Chassis Location Left Side (Dedicated Slot)
Weight 1.81 lbs (0.82 kg)

Engineering Advantages

  • Ride-Through Capability: The integrated capacitors provide a hold-up time of up to 40ms. This prevents nuisance controller resets during momentary DC bus brownouts or power transitions, maintaining process uptime in volatile power environments.

  • High-Density Current Delivery: This module delivers a substantial 8A at the 5.1V backplane rail. This high output supports fully populated 17-slot chassis containing multiple high-drain communication modules and processors without requiring a secondary power source.

  • Thermal Resiliency: The 1756-PB50 features advanced heat dissipation components. It operates at full capacity in ambient temperatures up to 50 °C and supports derated operation up to 60 °C, making it suitable for unconditioned industrial enclosures.

  • Direct Chassis Integration: The unit snaps directly into the dedicated power supply slot on the left side of any standard 1756 ControlLogix chassis. This design eliminates external wiring for logic power and ensures a low-impedance connection to the backplane.

FAQs

  • Can I use the 1756-PB50 in a redundant power supply configuration?

    No. The 1756-PB50 is a standard power supply. For redundant applications, you must use the 1756-PB75R or 1756-PSCA2 adapter system. This module is intended for standalone chassis power.

  • What type of fuse or circuit protection do you recommend for the input?

    To protect against the 30A inrush current and potential short circuits, install a fast-acting fuse or a high-magnetic trip circuit breaker rated appropriately for the 24V DC supply line.

  • Does this module provide power for field-side devices?

    No. The 1756-PB50 only provides power to the chassis backplane for internal module logic. You must provide a separate 24V DC source to power field-side actuators, sensors, and I/O terminal blocks.

  • How do I verify if the power supply is functioning correctly?

    The front panel includes a green "DC Power" LED. If the LED is off, check the 24V DC input terminals for voltage and ensure the module is fully seated in the chassis.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

UPS architecture dictates power reliability in process automation. Unplanned voltage sags cause immediate downtime, making robust power backup essential for PLC and DCS networks. This technical guide evaluates the operational principles, key architectures, and tradeoffs between Static and Dynamic Rotary UPS systems.
Read more
Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Signal integrity determines reliability in modern industrial automation. Unwanted electrical noise degrades sensor data, distorts 4-20 mA current loops, and drops fieldbus communications. Engineers working with PLC, DCS, and TSI systems must effectively mitigate these disturbances. This technical guide analyzes key internal and external noise sources affecting control systems.
Read more
Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Emergency stop (E-Stop) pushbuttons serve as vital safety devices in factory automation and process control plants. Functional safety standards mandate normally-closed (NC) contact blocks to ensure fail-safe operation during wiring breaks or power outages. However, mechanical degradation over time can trigger unexpected spurious trips, halting production lines without an actual emergency. Understanding the underlying causes of mechanical contact failure allows automation engineers to implement robust, fault-tolerant safety circuits.

Read more