Overview

The Allen-Bradley 1746-OA8 is a discrete AC output module designed for the SLC 500 series. It provides eight output channels organized into two groups, offering reliable switching for AC loads in industrial automation systems. With robust electrical ratings and fast response times, it is well-suited for general-purpose applications.

Technical Specifications

  • Manufacturer Allen-Bradley

  • Product Line SLC 500

  • Part Number 1746-OA8

  • Weight 0.20 kg (0.44 lbs)

  • Module Type Discrete AC Output Module

  • Number of Groups 2

  • Channels per Group 4

  • Nominal Output Voltage 120 / 240 VAC

  • Output Voltage Range 85–264 VAC

  • Backplane Current Consumption 185 mA at 5 VDC

  • ON Signal Delay (Resistive Load) 1 ms

  • OFF Signal Delay (Resistive Load) 11 ms

  • Continuous Current per Point 1.0 A at 30 °C (86 °F); 0.5 A at 60 °C (140 °F)

  • Continuous Current per Module 8.0 A at 30 °C (86 °F); 4.0 A at 60 °C (140 °F)

  • On-State Voltage Drop (Max) 1.5 V at 1.0 A

  • Surge Current per Point 10 A for 25 ms

  • Step Response 60 ms input, 2.5 ms output

Application Scenarios

  • General-purpose AC load control in manufacturing systems

  • Switching of lighting, heating, or motor loads

  • Integration into Allen-Bradley SLC 500 PLC systems for distributed control

FAQ

Q: How many outputs does the 1746-OA8 provide?  A: The module offers 8 outputs, divided into 2 groups of 4 channels each.

Q: What is the maximum current per channel?  A: 1.0 A at 30 °C and 0.5 A at 60 °C.

Q: Is this module suitable for inductive loads?  A: It is primarily designed for resistive loads, but can handle moderate inductive loads within rated specifications.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Main Components of a SCADA System in Industrial Automation

Main Components of a SCADA System in Industrial Automation

Discover the key components of a SCADA system and how sensors, RTUs, master units, and communication networks integrate to monitor and control industrial processes in real time.

Read more
Key Functions of a SCADA System in Industrial Automation

Key Functions of a SCADA System in Industrial Automation

Explore the four core functions of SCADA—data acquisition, communication, visualization, and control—and understand how this system powers industrial automation, process optimization, and remote supervision.

Read more
Instrumentation Earthing in Industrial Automation Systems

Instrumentation Earthing in Industrial Automation Systems

In industrial automation, earthing provides a safe, low-resistance path for electrical fault currents. It protects both equipment and personnel by diverting excessive current directly into the ground. Proper earthing is fundamental to PLC, DCS, and control system reliability, ensuring stable operation even under fault conditions.

Read more