Skip to content

What are you looking for?


You may also like

Schneider Electric LUCB05BL TeSys Ultra Advanced Control UnitSchneider Electric LUCB05BL TeSys Ultra Advanced Control UnitSchneider Electric LUCB05BL TeSys Ultra Advanced Control Unit
Schneider Electric LUCB05BL TeSys Ultra Advanced Control Unit
Schneider Electric LUCB05BL TeSys Ultra Advanced Control Unit
Schneider Electric LUCB05BL TeSys Ultra Advanced Control Unit

Schneider Electric LUCB05BL TeSys Ultra Advanced Control Unit


Only 10 left - Selling fast

PRODUCT SKU : LUCB05BL

PRODUCT TYPE : Motor Control Units

PRODUCT VENDOR : Schneider


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Schneider Electric LUCB05BL, also cataloged as the LUCB Advanced Control Unit, operates as a dedicated hardware component for 3-phase motor protection and thermal overload execution within TeSys Ultra power bases.

Hardware Specifications

Parameter Specification
Model LUCB05BL
Brand Schneider Electric
Origin France
Weight 113 g (0.113 kg)
Dimensions 45 mm x 66 mm x 60 mm (W x H x D)
Operating Temp -25 to +70 deg C
Power Consumption Heat dissipation: 2 W (with LUB12), 3 W (with LUB32/LUB38)
Rated Operational Voltage [Ue] 690 V AC (40 to 60 Hz)
Control Circuit Voltage [Uc] 24 V DC (Limits: 20 to 27 V DC operational, 14.5 V DC drop-out)
Motor Current Adjustment Range 1.25 to 5 A
Thermal Overload Class Class 10 (40 to 60 Hz, -25 to 70 deg C)
Tripping Threshold 14.2 x Ir +/- 20 %
Motor Power Rating 1.5 kW at 400-440 V AC, 2.2 kW at 500 V AC, 3 kW at 690 V AC
Control Current Consumption Closing: 130 mA (LUB12), 220 mA (LUB32/38); Sealed: 60 mA (LUB12), 80 mA (LUB32/38)
Insulation Voltage [Ui] 690 V (IEC 60947-6-2), 600 V (UL 60947-4-1 / CSA C22.2 No 60947-4-1)
Ingress Protection IP20 (front panel and wired terminals), IP40 (front panel outside connection zone)

Industrial Control & Bus Communication Characteristics

The LUCB05BL advanced control unit attaches directly via front-face plug-in mounting to LUB power bases and LU2B reversing contactor breakers. Internal current-sensing transformers provide phase failure sensitivity, phase imbalance protection, earth fault detection, and manual reset functions. Communication interface capabilities support real-time motor diagnostic transmission across Profinet and EtherNet/IP deterministic networks, maintaining backplane bus communication velocity and firmware flash compatibility across integrated starter configurations.

Frequently Asked Questions

Q: What are the control coil voltage operational thresholds for the LUCB05BL unit?

A: The rated control circuit voltage is 24 V DC, operating within strict limits of 20 to 27 V DC during active state execution and dropping out at 14.5 V DC.

Q: Which power bases and contactors are physically compatible with this control module?

A: The LUCB05BL plug-in module interfaces directly with LUB12, LUB32, LUB38, LUB120, LUB320, and LUB380 power bases, as well as LU2B12BL, LU2B32BL, and LU2B38BL reversing contactor breakers.

Q: What opening and closing times occur when the control unit acts on a power base?

A: Operating response times are rated at 35 ms for circuit opening and 70 ms for circuit closing across LUB12, LUB32, and LUB38 assemblies.

Field Installation Guidelines

  • Plug-In Mounting: Align the LUCB05BL unit with the front-face connector slot of the unpowered LUB or LU2B base unit and push firmly until the locking mechanism fully seats.
  • Control Circuit Wiring: Connect 24 V DC control supply leads to the designated control terminals. Ensure control circuit voltage remains between 20 V DC and 27 V DC during peak inrush (up to 220 mA) to prevent contact chatter.
  • Thermal Current Setting: Adjust the front dial to match the exact full-load current (FLA) of the connected 3-phase motor within the 1.25 A to 5 A scaling range before applying main line voltage up to 690 V AC.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Top 5 Operational Advantages of HMIs in Modern Factory Automation

Top 5 Operational Advantages of HMIs in Modern Factory Automation

HMIs bridge the gap between operators and complex industrial control networks. Modern factory automation relies on HMIs to deliver real-time visualization, precise control, and data analytics alongside PLC and DCS infrastructure. This technical guide explores five core operational benefits of deploying HMIs in manufacturing.
Read more
Importance of Safety Barriers in PLC and DCS Control Systems

Importance of Safety Barriers in PLC and DCS Control Systems

Process industries handle flammable gases and liquids, making electrical instrumentation a constant ignition risk. Engineers designing PLC and DCS networks must implement strict energy-limiting strategies. Intrinsic Safety barriers provide the critical interface that safeguards automation assets and prevents explosions.
Read more
Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

UPS architecture dictates power reliability in process automation. Unplanned voltage sags cause immediate downtime, making robust power backup essential for PLC and DCS networks. This technical guide evaluates the operational principles, key architectures, and tradeoffs between Static and Dynamic Rotary UPS systems.
Read more