Skip to content

What are you looking for?


You may also like

T8451 ICS Triplex Trusted TMR Digital Output ModuleT8451 ICS Triplex Trusted TMR Digital Output ModuleT8451 ICS Triplex Trusted TMR Digital Output Module
T8451 ICS Triplex Trusted TMR Digital Output Module
T8451 ICS Triplex Trusted TMR Digital Output Module
T8451 ICS Triplex Trusted TMR Digital Output Module

T8451 ICS Triplex Trusted TMR Digital Output Module


Only 10 left - Selling fast

PRODUCT SKU : T8451

PRODUCT TYPE : Digital Output Modules

PRODUCT VENDOR : ICS Triplex


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for high-integrity discrete load switching in safety-critical ESD and shutdown systems, the ICS Triplex T8451 (T8451 Digital Output Module) provides direct physical/electrical execution. The module drives up to 40 field-side channels partitioned into 5 independent power groups over an operational voltage range of 18 VDC to 32 VDC.

Hardware Specifications

Parameter Specification
Model T8451
Brand ICS Triplex
Origin United Kingdom
Weight 1.13 kg (Shipping Weight: 3.0 kg)
Dimensions 300 mm x 30 mm x 241 mm (11.8 in x 1.2 in x 9.5 in)
Operating Temp -5 deg C to +60 deg C (+23 deg F to +140 deg F)
Power Consumption 24 W (System Supply) / 24 W (Field Supply @ 1 A/ch)
System Supply Voltage 20 VDC to 32 VDC
Operational Field Voltage 18 VDC to 32 VDC (Max Withstanding: -1 VDC to +40 VDC)
Output Channels 40 Channels (5 Power Groups of 8 outputs)
Continuous Current Rating 2 A per channel (Max 8 A per power group)
Minimum On-State Load 50 mA
On-State Resistance 0.6 Ohm
Output Turn-On/Off Delay 0.5 ms
Sample Update Time 0.5 ms
Field Common Isolation +/-250 VDC Sustained Working / +/-2.5 kVDC Max Withstanding
Operating Humidity 5% to 95% RH non-condensing

High-Reliability Safety Control & TMR Architecture

The T8451 incorporates a triple modular redundancy (TMR) 2oo3 fault-tolerant architecture to achieve SIL3 certification within high-availability safety execution loops. Triplicated output channels utilize internal voter circuits and automatic electronic latching short-circuit protection to maintain continuous fail-safe state execution without dropping active control loops. Field-common galvanic isolation rated at +/-250 VDC sustained working voltage suppresses cross-talk and ground potential shifts, ensuring process field outputs execute deterministic shutoff logic during system fault events.

Frequently Asked Questions

Q: What are the current distribution limits per channel and per power group on the T8451 module?

A: Each individual output channel supports a maximum continuous load of 2 A, with the total combined load capped at 8 A per power group across the 5 independent output groups.

Q: How does the T8451 respond to an overcurrent or output short-circuit condition?

A: The module features automatic, electronic latching short-circuit protection that isolates the faulted channel to protect output switching hardware and surrounding control circuitry.

Q: Is external isolation required for installation of the T8451 in hazardous location field loops?

A: Yes. The module does not contain built-in intrinsic safety barriers; external Ex-i barriers must be wired in series with field loops requiring intrinsic safety protection.

Field Installation Guidelines

  1. Isolate field power and verify the 18 VDC to 32 VDC field voltage source before inserting the module into the active chassis slot.
  2. Ensure field load currents remain above the 50 mA minimum on-state threshold to maintain valid channel diagnostic state sensing.
  3. Route field output cables away from high-voltage AC lines to maintain channel-to-channel crosstalk suppression better than -40 dB.
  4. Securely seat the module retaining hardware into the rack frame to guarantee low-impedance frame grounding and continuous +/-2.5 kVDC isolation withstand capability.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

The Site Acceptance Test (SAT) represents the definitive handover stage in industrial automation projects. While the Factory Acceptance Test confirms cabinet hardware assembly off-site, the SAT validates real-world performance under live site conditions. Consequently, a structured execution strategy prevents equipment damage and guarantees seamless integration into plant operations.

Read more
Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

The Factory Acceptance Test (FAT) is a vital milestone in industrial automation that ensures custom PLC panels meet exact design specifications before dispatch. This guide outlines the step-by-step FAT procedure and key industry best practices to prevent costly site delays and ensure long-term operational success.

Read more
Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

System reliability directly determines operational profitability across high stakes process industries. Modern industrial automation platforms must eliminate single points of failure to prevent catastrophic shutdowns. Deploying fault tolerant architecture safeguards complex facilities against unexpected hardware glitches, network disruptions, and maintenance outages.

Read more