Skip to content

What are you looking for?


You may also like

469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay
469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay
469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay
469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay

469-P1-HI-A20-E-H | GE | Multilin 469 Motor Management Relay


Only 10 left - Selling fast

PRODUCT SKU : 469-P1-HI-A20-E-H

PRODUCT TYPE : Motor Management Relays

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE 469-P1-HI-A20-E-H, also cataloged as the 469 Motor Management Relay, operates as a dedicated hardware component for protection, control, and diagnostic tracking within electrical substation and motor control center networks. The device reads current, voltage, and thermal inputs to execute protection logic, managing electrical distribution through isolated digital inputs and analog outputs. Hardware features include an enhanced 40-character LCD interface and conformal coating for industrial environmental resilience.

Hardware Specifications

Parameter Specification
Model 469-P1-HI-A20-E-H
Brand GE Multilin
Origin Technical specifications determine final factory origin
Weight Physical enclosure mass varies by mounting configuration
Dimensions Standard 469 series panel cutout dimensions apply
Operating Temp -40 to +60 deg C
Power Consumption Control supply dependent
Control Power 90-300 VDC or 70-265 VAC
Line Frequency 48-62 Hz
Digital Inputs 9 opto-isolated digital inputs
Analog Outputs 4 selectable outputs (0-1 mA or 4-20 mA configurations)
Display Type Enhanced LCD (40 characters)
Environmental Protection Conformal coating for harsh environments
Storage Temp -40 to +80 deg C

Firmware Flash Compatibility and Deterministic Signal Processing

The internal microprocessor architecture maintains synchronous code execution, utilizing specialized memory blocks to guarantee firmware flash compatibility across standard motor protection configurations. Input monitoring runs on a strict internal clock to provide deterministic measurement tracking of thermal and electrical variables. The I/O backplane processing loops prevent runtime jitter during concurrent tracking of the 9 opto-isolated digital inputs and active analog output matrices.

Frequently Asked Questions

Q: Can the internal I/O modules or display board be extracted while the control power is applied?

A: No. The internal logic circuitry and backplane power traces do not support live hot-swapping. Control power (90-300 VDC or 70-265 VAC) must be completely isolated before servicing internal hardware components to avoid permanent electrical damage or erratic contact states.

Q: How do the opto-isolated digital inputs handle external electrical noise?

A: The 9 digital inputs are equipped with galvanic optical isolation to separate external field wiring loops from the internal logic processor bus. This design absorbs high-frequency transient spikes and prevents common-mode noise from disrupting internal control execution.

Field Installation Guidelines

  • Grounding Requirements: Connect a low-impedance copper conductor from the rear panel chassis grounding terminal directly to the main cubicle ground bus to establish an equipotential reference.
  • Shielding Protocol: Terminate the external shielding braid of all 4-20 mA analog output lines at the enclosure side only. Grounding both ends of the shield is prohibited to eliminate potential ground loop currents.
  • Cable Separation: Route all high-voltage power wiring (auxiliary supply and contact output circuits) through separate metal conduits away from low-voltage analog and digital signal wiring to reduce inductive coupling.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

System cabinet health checks ensure long-term reliability in industrial automation. Preventative maintenance prevents hardware degradation, communication loss, and unplanned outages in control networks. This guide outlines the standard operating workflow for inspecting PLC and DCS cabinets to maintain peak performance.
Read more
Top 5 Operational Advantages of HMIs in Modern Factory Automation

Top 5 Operational Advantages of HMIs in Modern Factory Automation

HMIs bridge the gap between operators and complex industrial control networks. Modern factory automation relies on HMIs to deliver real-time visualization, precise control, and data analytics alongside PLC and DCS infrastructure. This technical guide explores five core operational benefits of deploying HMIs in manufacturing.
Read more
Importance of Safety Barriers in PLC and DCS Control Systems

Importance of Safety Barriers in PLC and DCS Control Systems

Process industries handle flammable gases and liquids, making electrical instrumentation a constant ignition risk. Engineers designing PLC and DCS networks must implement strict energy-limiting strategies. Intrinsic Safety barriers provide the critical interface that safeguards automation assets and prevents explosions.
Read more