Product Description

The IC200UDD110 is a 28-point Micro PLC power supply module from GE Fanuc, designed for compact automation systems. It provides 16 positive logic 24V DC inputs and 12 transistor outputs, with high-speed counter support and integrated power supply for both the logic and field devices. This module ensures fast response times and reliable isolation for safe industrial operation.

Technical Specifications

  • Manufacturer: GE Fanuc

  • Model / Part Number: IC200UDD110

  • Product Type: 28-Point Micro PLC Power Supply

  • Inputs: Sixteen 24V DC positive logic inputs arranged in four groups of four

  • Outputs: Twelve transistor outputs, 24V DC. Two groups with separated incoming supply: four outputs per group at 0.5A max, two outputs at 1A max

  • High-Speed Counters: Up to four Type A or one Type A + one Type B

  • +24V DC Output Power Supply: 200 mA maximum for input circuits and user devices

  • Input Voltage Range: 0–30 VDC

  • Rated Input Voltage: 24 VDC nominal

  • Operational Voltage Range: 19.2–30 VDC, nominal 24 VDC (+10% / -43% input at V1, C1)

  • Isolation Voltage: 1500 V RMS between field and logic sides, 500 V RMS between groups

  • Response Time: 0.1 ms max (OFF to ON, ON to OFF, 24V DC, 0.2A)

  • Point-to-Point Isolation: None specified

  • Environmental Rating: Suitable for industrial PLC installations

Features

  • Compact Micro PLC design with combined I/O and power supply

  • Fast ON/OFF response for high-speed automation tasks

  • Separated output groups for flexible load management

  • Integrated +24V DC output supports field devices and internal circuits

  • High-voltage isolation between field and logic sections ensures safety

Applications

  • Small to medium PLC-controlled automation systems

  • Machine control panels requiring compact 28-point I/O modules

  • Industrial processes needing fast response digital inputs and transistor outputs

FAQ / Comparison

  • Q: How many outputs can be loaded at 1A?
    A: Two outputs per module can handle 1A, the rest are rated at 0.5A.

  • Q: Can this module support high-speed counters?
    A: Yes, up to four Type A counters or one Type A and one Type B.

  • Q: How does IC200UDD110 compare with IC200UDD100?
    A: IC200UDD110 adds separated output groups and higher total output flexibility compared to the IC200UDD100.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more