Skip to content

What are you looking for?


You may also like

Emerson EPXPNS001 PACSystems RSTi-EP PROFINET ScannerEmerson EPXPNS001 PACSystems RSTi-EP PROFINET ScannerEmerson EPXPNS001 PACSystems RSTi-EP PROFINET Scanner
Emerson EPXPNS001 PACSystems RSTi-EP PROFINET Scanner
Emerson EPXPNS001 PACSystems RSTi-EP PROFINET Scanner
Emerson EPXPNS001 PACSystems RSTi-EP PROFINET Scanner

Emerson EPXPNS001 PACSystems RSTi-EP PROFINET Scanner


Only 10 left - Selling fast

PRODUCT SKU : EPXPNS001

PRODUCT TYPE : Network Interface Modules

PRODUCT VENDOR : EMERSON


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for fieldbus network integration in PACSystems RSTi-EP platforms, the Emerson EPXPNS001 (EPXPNS001 PROFINET Scanner) provides direct physical/electrical execution. It establishes high-speed deterministic data transfer between the central controller and up to 64 local I/O modules via dual RJ-45 interfaces.

Hardware Specifications

Parameter Specification
Model EPXPNS001
Brand Emerson
Base Model EPXPNS001
Origin USA
Weight 220 g (7.76 oz)
Dimensions 52 mm x 76 mm x 120 mm
Operating Temp -20 to +60 deg C (-4 to +140 deg F)
Power Consumption Current consumption from system path (ISYS): 116 mA
Supply Voltage System/Inputs/Outputs: 20.4 VDC to 28.8 VDC
Fieldbus Protocol PROFINET Version 2.3 Class C I/O Device (IRT, RT)
Physical Interface 2 x RJ-45 ports, Micro USB 2.0 configuration interface
Transfer Rate Fieldbus: 100 Mbps max; System Bus: 48 Mbps max
Process Image Max 512 bytes input, max 512 bytes output
Max Module Capacity Up to 64 active I/O modules
Feed-in Current Max 10 A for input modules, max 10 A for output modules
Relative Humidity 5% to 95% non-condensing (DIN EN 61131-2)

Profinet / EtherNet/IP Deterministic Networks and I/O Density Scaling

The EPXPNS001 PROFINET Scanner maintains deterministic communication profiles using PROFINET Version 2.3 Class C protocol (RT/IRT) with selectable update rates down to 1 ms. Supporting Media Redundancy Protocol (MRP) ring topologies, the module handles process image exchanges of up to 512 bytes input and 512 bytes output. It scales I/O density by managing up to 64 local slices, bridging high-speed 100 Mbps network traffic down to the 48 Mbps RSTi-EP local system bus via galvanically isolated physical layers.

Frequently Asked Questions

Q: What is the minimum PROFINET I/O update rate required for bumpless operation in an MRP ring topology?

A: The minimum recommended I/O update rate for bumpless failover in a Media Redundancy Protocol (MRP) ring configuration is 32 ms or slower for the EPXPNS001 scanner.

Q: How do the PWR, SF, and BF LED indicators reflect the hardware operational status?

A: A solid green PWR LED indicates active logic supply; a solid red SF LED indicates a system fault, scanner module error, or active force mode; and a solid red BF LED signals a loss of physical connection to the fieldbus network.

Q: What wire gauge range is supported by the spring-style connection terminals?

A: The spring-style terminals accept single-wired or fine-wired conductors with cross-sections ranging from 0.14 mm2 to 1.5 mm2 (AWG 26 to AWG 16).

Field Installation Guidelines

  1. Mount the scanner onto a standard 35 mm DIN rail inside a protective industrial panel enclosure.
  2. Connect the 20.4 VDC to 28.8 VDC power supply wires to the spring terminals, ensuring proper wire strip lengths between 0.14 mm2 and 1.5 mm2.
  3. Insert RJ-45 Ethernet network cables into Port 1 and Port 2 until the locking tabs snap securely.
  4. Align adjacent RSTi-EP I/O module slice connectors and slide them firmly onto the right side of the scanner to engage the internal system bus.
  5. Connect the functional earth terminal to the central enclosure ground rail to ensure full noise immunity and surge suppression.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying Programmable Logic Controllers: Comprehensive Guide to PLC Classification and Selection in Industrial Automation

Demystifying Programmable Logic Controllers: Comprehensive Guide to PLC Classification and Selection in Industrial Automation

Modern industrial automation heavily relies on Programmable Logic Controllers (PLCs) to drive factory floor efficiency. Over my 15 years as an industrial automation expert working with DCS, TSI, and control systems, I have seen PLCs evolve into the central nervous system of modern manufacturing. Selecting the right controller requires a deep understanding of PLC types based on physical size, hardware architecture, and power supply configurations.

Read more
Comprehensive Guide to PLC Types in Modern Industrial Automation

Comprehensive Guide to PLC Types in Modern Industrial Automation

Modern industrial automation relies on programmable logic controllers to govern critical factory operations. System integrators classify PLCs based on scale, hardware architecture, and power supply design. Understanding these core categories enables automation engineers to select the right control system architecture. Consequently, proper hardware selection optimizes performance while minimizing long-term operational costs.

Read more
Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Modern control systems rely heavily on seamless interprocess communication to exchange operational data between software programs. Microsoft first introduced the Dynamic Data Exchange (DDE) protocol in 1987 to enable real-time data sharing. In factory automation, DDE served as an early bridge between control software and Windows desktop applications. Therefore, understanding DDE mechanics provides crucial insights into how legacy industrial networks established software-level connectivity.

Read more