Product Details

Configured for pulse frequency counting and accumulation tasks in ABB 800xA distributed control networks, the ABB DP840 3BSE028926R1 (DP840 Pulse Counter Module) provides direct physical/electrical execution across 8 isolated field input channels.

Hardware Specifications

Parameter Specification
Model DP840 (3BSE028926R1)
Brand ABB
Origin Sweden
Weight 0.15 kg
Dimensions 45 mm x 102 mm x 119 mm
Operating Temp 0 to 55 deg C
Power Consumption 4 W maximum power dissipation
Channels 8 pulse counting channels
Nominal Voltage 24 VDC (19.2 to 32 VDC range)
Modulebus +5 V Current 115 mA
External 24 V Current 97 mA + external load
Isolation Groupwise isolated from ground (50 V rated insulation, 500 VAC dielectric test)
Maximum Field Cable 200 meters
Accuracy Error Max absolute error 500 ppm at PRIT = 10 ms (oscillator drift 120 ppm + 5 ppm/year)
Compatibility S800 I/O MTUs: TU810, TU812, TU814, TU818, TU830, TU833, TU842, TU843, TU844, TU845, TU852, TU854

Backplane Bus Communication Velocity and I/O Density Scaling

The DP840 module interface maintains deterministic Modulebus communication velocity, allowing high-density pulse train processing without degrading backplane scanning cycles. Integrated hardware counters offload high-frequency pulse calculation from the primary AC 800M controller CPU, enabling scalable I/O density scaling across redundant S800 I/O clusters. Firmware flash compatibility ensures consistent channel supervision and process voltage diagnostic reporting through standard ABB 800xA control software libraries.

Frequently Asked Questions

Q: Does the DP840 module support redundant configuration in S800 I/O racks?

A: Yes, the DP840 supports hardware redundancy when paired with redundant Module Terminal Units such as the TU842, TU843, TU844, or TU845.

Q: What is the maximum permitted field cable distance for pulse inputs on this card?

A: The maximum field cable length for input pulse wiring is limited to 200 meters.

Q: How does the internal power distribution behave when supplying power to field sensors?

A: The DP840 provides built-in current-limited sensor power outputs on each input channel to prevent localized short circuits from affecting the backplane logic power supply.

Field Installation Guidelines

  1. Confirm the mechanical keying code CF matches the designated slot position on the Module Terminal Unit (MTU) before insertion.
  2. Disconnect Modulebus power and process voltage feeds prior to inserting or removing the DP840 module from the MTU baseplate.
  3. Align the module housing with the locking guide rails of the MTU and press firmly until the locking mechanism clicks into position.
  4. Ensure signal wiring cable shields are grounded at the field cable termination bar using low-impedance grounding clamps.
  5. Verify process voltage levels (19.2 to 32 VDC) on external terminals before energizing the module.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Top 5 Operational Advantages of HMIs in Modern Factory Automation

Top 5 Operational Advantages of HMIs in Modern Factory Automation

HMIs bridge the gap between operators and complex industrial control networks. Modern factory automation relies on HMIs to deliver real-time visualization, precise control, and data analytics alongside PLC and DCS infrastructure. This technical guide explores five core operational benefits of deploying HMIs in manufacturing.
Read more
Importance of Safety Barriers in PLC and DCS Control Systems

Importance of Safety Barriers in PLC and DCS Control Systems

Process industries handle flammable gases and liquids, making electrical instrumentation a constant ignition risk. Engineers designing PLC and DCS networks must implement strict energy-limiting strategies. Intrinsic Safety barriers provide the critical interface that safeguards automation assets and prevents explosions.
Read more
Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

Static UPS vs. Rotary UPS: Technical Evaluation for Industrial Automation

UPS architecture dictates power reliability in process automation. Unplanned voltage sags cause immediate downtime, making robust power backup essential for PLC and DCS networks. This technical guide evaluates the operational principles, key architectures, and tradeoffs between Static and Dynamic Rotary UPS systems.
Read more