Skip to content

What are you looking for?


You may also like

3BSE008512R1 | ABB | DI820 S800 Digital Input Modules3BSE008512R1 | ABB | DI820 S800 Digital Input Modules3BSE008512R1 | ABB | DI820 S800 Digital Input Modules
3BSE008512R1 | ABB | DI820 S800 Digital Input Modules
3BSE008512R1 | ABB | DI820 S800 Digital Input Modules
3BSE008512R1 | ABB | DI820 S800 Digital Input Modules

3BSE008512R1 | ABB | DI820 S800 Digital Input Modules


Only 10 left - Selling fast

PRODUCT SKU : DI820 3BSE008512R1

PRODUCT TYPE : Digital Input Modules

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB DI820 3BSE008512R1, also cataloged as the DI820 Digital Input Modules, operates as a dedicated hardware component for 120 VAC / 110 VDC signal acquisition and field discrete monitoring within ABB S800 I/O platforms.

Hardware Specifications

Parameter Specification
Model DI820
Part Number 3BSE008512R1
Brand ABB
Product Type Digital Input Modules
Origin Sweden
Weight 0.18 kg (0.4 lbs)
Dimensions 45 x 119 x 102 mm (111 mm depth including connector)
Operating Temp 0 to +55 deg C
Power Dissipation Typ. 2.8 W
Signal Specification 120 VAC / 110 VDC
Number of Channels 8 channels (Current sinking, individually isolated)
Input Impedance 12 kOhm (AC) / 39 kOhm (DC)
Input Voltage Range "0" 0 to 30 VAC, 0 to 20 VDC
Input Voltage Range "1" 77 to 130 VAC, 75 to 145 VDC
Selectable Digital Filter 2, 4, 8, 16 ms
Modulebus Current Consumption 50 mA (+5 VDC), 0 mA (+24 VDC)
Compatible Module Termination Units TU811, TU813, TU831, TU839, TU851

Backplane Bus Communication Velocity and Channel Isolation

The 8-channel input interface incorporates individual channel-to-channel isolation with a 250 V rated insulation profile and 2000 VAC dielectric test withstand limit. Data processing across the +5 VDC Modulebus backplane maintains high backplane bus communication velocity and firmware flash compatibility during controller scanning. The internal logic handles digital filtering delays (2 to 16 ms) to prevent contact bounce from compromising high-density I/O channel states.

Frequently Asked Questions

Q: What is the power draw of the DI820 module from the +5 VDC Modulebus?

A: The module consumes 50 mA from the +5 VDC Modulebus backplane rail, with zero consumption on the +24 VDC bus lines.

Q: Which Module Termination Units (MTUs) accept the DI820 digital input card?

A: The module interfaces with TU811, TU813, TU831, TU839, and TU851 termination units using mechanical keying code AB.

Q: Are individual channels on the DI820 galvanically isolated from each other?

A: Yes, all 8 input channels are individually isolated, preventing common-mode fault propagation between discrete field loops.

Field Installation Guidelines

  1. Disconnect Modulebus power and field voltage sources before locking the DI820 module onto its designated MTU base.
  2. Verify that the mechanical keying code on the Module Termination Unit is set to AB prior to insertion.
  3. Align the 0.18 kg module and press firmly into the MTU guide slots until the top locking latch fully engages.
  4. Limit field cable runs to a maximum of 200 meters for AC circuits (100 pF/m limit) and 600 meters for DC signals.
  5. Keep AC discrete input field wiring separated from low-voltage communication cabling by a minimum distance of 200 mm.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more