Skip to content

What are you looking for?


You may also like

Yokogawa VM2*D Analog Input Module Board CardYokogawa VM2*D Analog Input Module Board CardYokogawa VM2*D Analog Input Module Board Card
Yokogawa VM2*D Analog Input Module Board Card
Yokogawa VM2*D Analog Input Module Board Card
Yokogawa VM2*D Analog Input Module Board Card

Yokogawa VM2*D Analog Input Module Board Card


Only 10 left - Selling fast

PRODUCT SKU : VM2*D

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Yokogawa VM2*D, also cataloged as the VM2D Multipoint I/O Module, operates as a dedicated hardware component for HART-enabled analog signal acquisition and control within CENTUM VP and CS 3000 DCS platforms. It conditions 4-20 mA loop signals and extracts digital field telemetry, routing real-time process data directly across system control station backplanes.

Hardware Specifications

Parameter Specification
Model VM2*D
Brand Yokogawa
Origin Japan
Weight 1.36 kg
Dimensions 356 mm x 178 mm x 25 mm
Operating Temp -10 to 55 deg C
Power Consumption 24 VDC
I/O Type Analog (4-20 mA) / HART
Redundancy Dual-redundant capable
Calibration Storage Factory/User-defined non-volatile storage

4-20 mA HART Loop Protocol and Channel Isolation

The VM2*D facilitates high-precision process control by executing 16-bit analog-to-digital conversion and HART protocol data extraction from smart field instruments. The module architecture incorporates channel-to-channel isolation to suppress electromagnetic interference and prevent common-mode voltage contamination across the backplane. By leveraging integrated cold junction compensation (CJC) for temperature-sensitive signal paths and HART loop protocol connectivity, the module enables real-time diagnostic monitoring of field-mounted sensors. The dual-redundant design ensures synchronized state execution, allowing the system to maintain stable control outputs even during individual module fault events within the DCS control station.

Frequently Asked Questions

Q: Does the VM2D support online hot-swapping?

A: In redundant configurations, the VM2D allows for module replacement without shutting down the entire control station; however, verify the specific DCS rack backplane version and software configuration for safe extraction procedures.

Q: Is the HART protocol active on all analog channels?

A: Yes, the module is engineered to provide simultaneous analog loop control and digital HART data transmission, facilitating device configuration and diagnostic data logging without interrupting the primary control signal.

Q: How is the calibration data stored within the module?

A: The module utilizes non-volatile memory to retain both factory-provided calibration constants and user-defined offsets, ensuring immediate signal accuracy upon power-on or module swapping.

Field Installation Guidelines

  • ESD Protection: Always wear a grounded ESD wrist strap before handling the module board to prevent static damage to internal semiconductor devices.
  • Rack Seating: Slide the card along the guide rails into the backplane sub-rack slot. Engage retaining fasteners fully to maintain consistent earth ground continuity.
  • Shield Grounding: Terminate signal cable shields at a single ground bar location within the panel to suppress ground loop currents across the 4-20 mA loops.
  • Separation Restrictions: Maintain physical separation between 24 VDC analog/HART field wiring and AC power cables within cabinet wiring trunks to prevent cross-talk.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redefining Control Systems: The Rise of Flexible I/O Modules in Industrial Automation

Redefining Control Systems: The Rise of Flexible I/O Modules in Industrial Automation

Conventional input-output architectures often limit engineering agility and inflate long-term inventory costs. Today, Flexible Input/Output Modules (FIOM) are transforming how control system engineers design, commission, and maintain automation infrastructure. By allowing individual channel software configuration, FIOM technology bridges the gap between rigid hardware design and dynamic plant requirements.

Read more
Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Supervisory Control and Data Acquisition (SCADA) systems form the digital backbone of modern industrial automation. They collect critical field data, transmit signals across vast distances, and empower plant operators with real-time process visibility. Across modern infrastructures, SCADA solutions streamline centralized control and maintain continuous operational uptime.

Read more
Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

In industrial automation, connecting physical hardware with high-level software remains a primary operational challenge. Factories utilize programmable logic controllers (PLCs), distributed control systems (DCS), human-machine interfaces (HMIs), and smart sensors from diverse vendors. These devices often speak different proprietary protocols. Open Platform Communications (OPC) servers solve this interoperability challenge by standardizing how data flows across factory networks.

Read more