The YOKOGAWA AI-917-00 serves as the primary AI-917 Analogue Input Module utilized to execute multi-channel analog signal acquisition and data conversion across Yokogawa control platforms. The single Eurocard format hardware features four analog input channels and four analog output channels, supporting 0-20 mA current loops and 0-10 V voltage ranges with 10-bit resolution.

Hardware Specifications

Parameter Specification
Model AI-917-00
Brand YOKOGAWA
Origin Japan
Weight 0.25 kg
Dimensions 160 x 100 x 20 mm (Single Euro format 4TE)
Operating Temp -10 to 60 deg C
Power Consumption 0.5 W (24 VDC internal bus supply)
Input Channels 4 channels (0-20 mA or 0-10 V)
Output Channels 4 channels
Connector Type DIN 41612 Bauform F 48p
Current Signal Span 0 to 20 mA (50 ohm impedance, max 50 mA)
Voltage Signal Span 0 to 10 V (5.5 kohm impedance, max 30 V)
Resolution 10 bits (1024 points over 21.6 mA / 10.8 V)
Accuracy +/-0.2% +/-1 bit
Local Display 2-row LCD display, programmable LEDs

4-20 mA HART Loop Protocol and Channel-to-Channel Isolation

The AI-917-00 architecture provides structured signal isolation to maintain data integrity when interfacing with 4-20 mA HART loop protocol transmitters and 0-10 V field devices. Integrated 10-bit Analog-to-Digital (A/D) converters sample incoming signal levels against a stable reference, while digital signal conditioning suppresses high-frequency line noise. Channel-to-channel isolation principles isolate current and voltage loops, preventing ground potential differences from corrupting converted 8-bit serial data transmitted across the system backplane.

Frequently Asked Questions

Q: What is the physical mounting standard and backplane connector format for the AI-917-00 module?

A: The module is built in a single Eurocard 4TE form factor (160 x 100 x 20 mm) and connects to the backplane via a 48-pin DIN 41612 Bauform F connector.

Q: What resolution and conversion accuracy does the AI-917-00 provide for current and voltage inputs?

A: The module operates with 10-bit resolution (1024 steps across 21.6 mA or 10.8 V) and delivers an overall measurement accuracy of +/-0.2% +/-1 bit.

Q: How are local diagnostics and measurement values displayed on the module front panel?

A: A two-row LCD display shows numeric values on the first row and alphanumeric characters on the second row, supplemented by programmable LED status indicators.

Field Installation Guidelines

De-energize the rack backplane power supply before inserting or removing the AI-917-00 module from the card cage. Align the PCB edge with the Eurocard card cage guide rails and slide the module smoothly until the 48-pin DIN 41612 Bauform F connector seats fully into the mating backplane receptacle. Tighten front panel retaining screws to ensure chassis earthing continuity. Route all 0-20 mA current loop and 0-10 V voltage wiring using shielded cables, grounding the shielding braid at a single earth point on the cabinet earthing bar. Maintain separation between low-level analog wiring and high-voltage AC conductors.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Modern control systems rely heavily on seamless interprocess communication to exchange operational data between software programs. Microsoft first introduced the Dynamic Data Exchange (DDE) protocol in 1987 to enable real-time data sharing. In factory automation, DDE served as an early bridge between control software and Windows desktop applications. Therefore, understanding DDE mechanics provides crucial insights into how legacy industrial networks established software-level connectivity.

Read more
Demystifying CPU Communication Ports in Siemens PLC Architectures

Demystifying CPU Communication Ports in Siemens PLC Architectures

Industrial automation relies heavily on robust data exchange between devices. Without seamless connectivity, field instruments, network switches, human-machine interfaces, and programmable logic controllers cannot coordinate effectively. Therefore, understanding the various CPU communication ports available in Siemens hardware ensures efficient factory automation design and seamless system integration.

Read more
Mastering the Siemens PLC Scan Cycle: How the CPU Executes Automation Programs

Mastering the Siemens PLC Scan Cycle: How the CPU Executes Automation Programs

Industrial automation relies heavily on programmable logic controllers (PLCs) to manage complex manufacturing processes. Many engineers dive straight into programming without mastering the underlying architecture. However, understanding how a PLC CPU executes a program ensures reliable system design. Therefore, mastering the scan cycle optimizes both performance and troubleshooting in modern control systems.

Read more