Skip to content

What are you looking for?


You may also like

Yokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input ModuleYokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input ModuleYokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input Module
Yokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input Module
Yokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input Module
Yokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input Module

Yokogawa AAT141-S00 CENTUM VP/FIO TC/mV/RTD Input Module


Only 10 left - Selling fast

PRODUCT SKU : AAT141-S00

PRODUCT TYPE : TC/mV/RTD Input Module

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Overview

The Yokogawa AAT141-S00 functions as a high-versatility analog input interface for the CENTUM VP and CS 3000 FIO (Field network I/O) architectures. This module provides 16 fully isolated channels designed to capture low-level signals from Thermocouples (TC), millivolt (mV) sources, and Pt100 RTDs. It serves as a critical bridge between field temperature sensors and the Distributed Control System (DCS), ensuring high-precision data acquisition for complex process loops. We supply this module in 100% brand new, original condition to guarantee the measurement accuracy and structural integrity required for mission-critical industrial environments.

Part Number Breakdown: AAT141-S00

  • AAT141: TC/mV/RTD Input Module (16-channel, Isolated).

  • -S: Standard type for general industrial applications.

  • 0: Always 0 (Standard configuration).

  • 0: Basic type without specialized conformal coating.

Technical Specifications

  • Number of Channels: 16 (Fully Isolated)

  • Thermocouple Support: Types J, K, E, B, R, S, T, and N

  • mV Range: -100 to 150 mV / -20 to 80 mV

  • RTD Compatibility: Pt100 (3-wire type)

  • Measurement Accuracy: TC: ±30 μV | RTD: ±120 mΩ | mV: ±30 μV (span -20 to 80 mV)

  • Input Resistance: 2 MΩ or larger (Both Power ON and Power OFF)

  • Wiring Resistance: 1000 Ω or less (TC/mV) | 40 Ω or less per wire (RTD)

  • Condition: 100% Brand New Original

Engineering Advantages

The AAT141-S00 eliminates common signal acquisition failures through advanced hardware engineering and multi-protocol support:

  • Universal Input Flexibility: Unlike single-purpose modules, the AAT141-S00 handles TC, mV, and RTD signals on a single hardware platform. This versatility allows engineers to mix different sensor types within the same I/O nest, significantly reducing the variety of spare parts required on-site.

  • Superior Galvanic Isolation: Every channel maintains total electrical isolation from the system backplane and neighboring channels. This architecture blocks ground loops and prevents high-voltage transients in the field from damaging the core DCS electronics.

  • High Impedance Stability: The module maintains an input resistance of 2 MΩ or larger regardless of power status. This high impedance prevents signal loading errors, ensuring that the voltage measured by the DCS accurately reflects the actual process temperature at the sensor tip.

  • High-Resolution Thermal Tracking: With a TC accuracy of ±30 μV, this module detects minute temperature shifts in reactors, boilers, and furnaces. This precision enables the control system to execute tighter PID loops, improving overall product yield and energy efficiency.

FAQs

  • Can I connect both Thermocouples and RTDs to the same module?

    Yes. The AAT141-S00 supports Thermocouples, mV signals, and 3-wire Pt100 RTDs. You can configure the input type for each channel via the CENTUM VP software to match your field instrumentation requirements.

  • Does this module require a specific terminal block for Cold Junction Compensation?

    Yes. To maintain the specified TC accuracy, you must use a terminal block equipped with a built-in Cold Junction Compensation (CJC) sensor. This allows the module to accurately calculate the absolute temperature from the thermocouple’s millivolt output.

  • How does the 3-wire RTD connection improve accuracy?

    The 3-wire configuration allows the AAT141-S00 to measure and subtract the lead-wire resistance from the total circuit resistance. This compensation ensures that the DCS calculates the temperature based solely on the Pt100 sensor's resistance, even over long cable runs.

  • Is this a genuine Yokogawa factory-sealed unit?

    Absolutely. We guarantee that every AAT141-S00 is 100% brand new and original. Each module arrives in its original factory packaging and includes a full 1-year warranty for your peace of mind.

 

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Choosing the Right Controller: PLC vs. Motion Controller in Industrial Automation

Choosing the Right Controller: PLC vs. Motion Controller in Industrial Automation

Selecting the optimal control architecture is a foundational decision in industrial automation. Engineers must frequently choose between a Programmable Logic Controller (PLC) and a dedicated Motion Controller. While both systems manage machinery, their underlying design philosophies differ significantly, impacting performance, scalability, and system integration.

Read more
Mastering PLC Power Supply Architectures and Operating Voltages

Mastering PLC Power Supply Architectures and Operating Voltages

Selecting the correct operating voltage is a critical step in designing reliable industrial automation systems. Whether you are working with a compact PLC or a large-scale DCS, your power architecture dictates the system's longevity. In this guide, we explore the standard voltage ranges and power distribution strategies required to maintain stable factory automation operations.

Read more
Optimizing Power Supply Sizing for Industrial Automation Systems

Optimizing Power Supply Sizing for Industrial Automation Systems

The power supply is the silent heartbeat of any industrial automation system. While engineers often prioritize processors and communication protocols, a stable power architecture remains the most critical factor for long-term reliability. In my 15 years of experience, I have found that neglecting power supply sizing often leads to ghost errors, intermittent field device failures, and costly production downtime.

Read more