Product Details
Product Description
The PS69-DPS module from ProSoft Technology is a PROFIBUS DP-V1 slave communication interface designed for Allen Bradley CompactLogix systems. It provides reliable PROFIBUS connectivity with robust compliance to international standards, making it suitable for demanding industrial environments.
Key Specifications
-
Manufacturer: Allen Bradley / ProSoft Technology
-
Model: PS69-DPS
-
Part Number: PS69-DPS
-
Product Type: PROFIBUS DP-V1 Slave Communication Module
-
Processor: EC1-160P with integrated ASPC2
-
PROFIBUS Interface: RS-485, up to 12 Mbps, potential-free (EN 50170 compliant)
-
Diagnostic Interface: RS-232, PS/2 Mini-DIN female connector, 9600 baud, non-isolated
-
Power Supply: 260 mA @ +5 V ±5%
-
Power Supply Distance Rating: 6 (no more than six modules away from the 1769 power supply)
-
Module Format: Standard 1769 single-slot module
-
Electromagnetic Compliance:
-
Burst: EN 61000-4-4, 2 kV, 5 kHz
-
Surge: EN 61000-4-5, 2 kV common mode, 1 kV differential mode
-
ESD: EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
-
Radiated/Conducted Immunity: EN 61000-4-3, 10 V/m (30–1000 MHz, 80% AM, 1 kHz sinewave); EN 61000-4-6, 10 V (0.15–30 MHz)
-
Radiated/Conducted Emission: EN 55011 Class A
-
Mechanical Resistance:
-
Vibration: IEC 600068-2-6, 10–150 Hz, ±0.75 mm, ±1 g, 1 octave/min
-
Shock: IEC 600068-2-27, 15 g, 11 ms
-
Operating Temperature: 0–60°C (32–140°F)
-
Storage Temperature: –40–85°C (–40–185°F)
-
Relative Humidity: 5–95% non-condensing
Core Features
-
PROFIBUS DP-V1 slave functionality for CompactLogix systems
-
Integrated diagnostic interface for troubleshooting and monitoring
-
Compliance with EN and IEC standards for EMC, ESD, surge, and vibration resistance
-
Compact single-slot design for efficient rack installation
-
Reliable operation across industrial temperature and humidity ranges
Application Scenarios
-
Integration of PROFIBUS DP-V1 slave devices into CompactLogix controllers
-
SCADA and distributed control systems requiring PROFIBUS connectivity
-
Industrial automation environments in petrochemical, food processing, and manufacturing sectors
FAQ
-
Q: What is the maximum PROFIBUS data rate supported? A: Up to 12 Mbps.
-
Q: How far can the module be installed from the power supply? A: No more than six modules away from the 1769 power supply.
-
Q: Does the module include diagnostic capabilities? A: Yes, via an RS-232 Mini-DIN interface.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.