PRODUCT SKU : NFTI3S-00

PRODUCT TYPE : Analog Input Module

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Overview

The Yokogawa NFTI3S-00 functions as a high-density analog input interface for the STARDOM FCN autonomous controller series. This module integrates up to 16 channels, converting field sensor signals into precise digital data for real-time process monitoring. We supply this unit as 100% Brand New and Original, ensuring your control system maintains peak performance without the risks associated with refurbished hardware.

Part Number Breakdown

The NFTI3S series utilizes a modular suffix system to define specific hardware capabilities:

Code Definition
NFTI3S Base Model: 16-Channel Analog Input Module
-0 Standard Type
0 Basic configuration (No specialized explosion-proof coating)

Technical Specifications

The NFTI3S-00 offers high-speed data acquisition with the following technical parameters:

  • Channels: 16 non-isolated input channels

  • Input Signals: 4 to 20 mA / 1 to 5 V DC

  • Accuracy: ±0.2% of full scale

  • Resolution: 12-bit A/D conversion

  • Data Refresh Cycle: 20 ms (Ideal for dynamic process loops)

  • Input Impedance: 250 Ω (Power ON) / 300 kΩ (Power OFF)

  • Isolation: Optical isolation between input and system circuitry

  • Operating Temperature: -10 to +60°C

  • Current Consumption: 350 mA at 5 V DC / 500 mA at 24 V DC

Engineering Advantages

The NFTI3S-00 solves specific field integration challenges through superior engineering:

  • High-Density Signal Management: By packing 16 channels into a single 0.3 kg module, this unit maximizes I/O density. Engineers reduce the total number of racks required, significantly lowering cabinet hardware costs.

  • Enhanced Signal Integrity: Optical isolation protects your system logic from field-side electrical surges and noise. The module withstands 1000 V AC for one minute, preventing ground loops from damaging the central processor.

  • Rapid Response Times: With a 50 ms step response time and a 20 ms refresh cycle, the NFTI3S-00 tracks fast-changing variables like pressure spikes or flow fluctuations, enabling more precise PID control.

  • Flexible Field Termination: The module supports both pressure clamp terminals and MIL connector cables, allowing for rapid pre-wiring or traditional point-to-point field connections depending on the project scale.

FAQs

  • Does this module support both current and voltage inputs simultaneously?

    Yes, the NFTI3S-00 accepts both 4-20 mA and 1-5 V DC signals. However, ensure that the external wiring and software configuration match the specific signal type for each channel to maintain accuracy.

  • How does the module handle power failure?

    The module features high input impedance (300 kΩ) when powered off. This design prevents the module from loading down the remaining field loops or causing signal drops in multi-drop configurations during maintenance.

  • Is this a current-version product for the STARDOM series?

    Absolutely. This is a 100% brand new, current-generation NFTI3S-00 module. It fully supports the latest FCN-500 and FCN-RTU controllers within the Yokogawa STARDOM architecture.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more