PRODUCT SKU : IC200MDD843E

PRODUCT TYPE : Digital I/O Cards

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE IC200MDD843E, also cataloged as the IC200MDD843 Discrete Mixed Module, operates as a dedicated hardware component for discrete signal switching and relay output execution within GE VersaMax control networks.

Hardware Specifications

Parameter Specification
Model IC200MDD843E
Brand GE (GE Fanuc / Emerson)
Origin USA
Weight 0.23 kg (0.50 lbs)
Dimensions 4.3 in x 1.956 in x 2.63 in (excluding carrier and connectors)
Operating Temp Standard industrial operating range
Power Consumption Rack-mounted backplane power; up to 190 mA backplane current draw
Total I/O Points 16 points (10 inputs, 6 outputs)
Input Type Positive logic / sourcing inputs
Output Type Fixed coil relays with moving armature and silver alloy contacts
Output Current Rating Up to 8 A total output current
Maximum Response Speed 10 ms
Switching Frequency Maximum 20 cycles per minute with inductive load
Terminal Interface 18 Type A field wiring terminals; additional Type B via shorting bar
Internal Protection No internal fuses or snubber circuits; no channel-to-channel isolation

Suffix Breakdown & Model Matrix

Base Model Suffix Revision Hardware Description
IC200MDD843 A / B / C / D Early hardware revisions of 16-point discrete mixed module
IC200MDD843 E Updated revision with enhanced component tolerance and manufacturing lifecycle updates

Backplane Bus Communication Velocity & Deterministic Network Execution

The IC200MDD843E module routes discrete field signals directly across the VersaMax backplane, drawing up to 190 mA from the backplane rail based on active input and relay coil states. The internal bus architecture provides predictable signal transfer to maintain high backplane bus communication velocity across local and expansion racks.

Full compatibility with Profinet / EtherNet/IP deterministic networks via VersaMax network interface modules ensures deterministic scan times and low-latency digital update rates. Integrated board firmware maintains strict firmware flash compatibility across controller revisions, permitting flexible I/O density scaling across high-density mixed field points without processing delay.

Frequently Asked Questions

Q: What are the current draw and power source requirements for the IC200MDD843E module?

A: Logic circuits draw up to 190 mA from the rack backplane supply depending on active I/O count, while field loads require an external power source connected to the module terminal block.

Q: Does the IC200MDD843E feature onboard fuses, snubbers, or channel isolation?

A: No. The module does not contain internal snubbers, onboard fuses, or channel-to-channel isolation. External suppression and fusing must be installed on field wiring loops.

Q: What contact rating and response speed apply to the 6 relay output points?

A: The outputs use silver alloy relay contacts rated for up to 8 A total current capacity, with a maximum response speed of 10 ms and a maximum switching rate of 20 cycles per minute under inductive loads.

Field Installation Guidelines

  1. Power Isolation: Disconnect primary rack backplane power and external 24 VDC/120 VAC field power before mounting or removing the module from its carrier base.
  2. Carrier Mounting: Align the module side slots with the VersaMax carrier board tracks and press firmly down until the latch mechanism locks into position.
  3. Field Wiring: Connect positive logic sourcing inputs and relay output load lines to the 18 Type A terminals. Install external fuse links on each output channel to protect relay contacts.
  4. Inductive Suppression: Install external RC snubbers or flyback diodes across external inductive loads to prevent contact arcing and voltage transient reflection back to the module.
  5. Electrostatic Protection: Wear a grounded anti-static wrist strap connected to an unpainted metal frame point when setting up field wiring or handling unshielded hardware.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Centralized vs Decentralized Automation Systems: Architectural Trade-Offs in Modern Industrial Control

Centralized vs Decentralized Automation Systems: Architectural Trade-Offs in Modern Industrial Control

Industrial automation relies heavily on robust control architectures to manage complex processes efficiently. Engineers must choose between centralized and decentralized topologies when designing plant automation. This decision directly impacts system reliability, scalability, and long-term maintenance costs.

Read more
Engineering a Process Control System Philosophy: Principles and Operational Impact

Engineering a Process Control System Philosophy: Principles and Operational Impact

A Process Control System (PCS) Philosophy serves as the foundational blueprint for modern plant engineering. During the design and construction phases, this document establishes clear guidelines for instrumentation and control (I&C) teams. Consequently, a well-defined philosophy directly dictates overall operational stability, maintenance efficiency, and future expansion capabilities across heavy process industries.

Read more
Engineering MCC Signal Interface Terminations in Modern Process Automation

Engineering MCC Signal Interface Terminations in Modern Process Automation

Industrial manufacturing plants rely on Motor Control Centers (MCC) to drive critical electrical loads. Plant engineers must interface these MCC motor starters and drives with central control systems. Standardizing the Signal Interface Termination (SIT) architecture ensures seamless command delivery and feedback monitoring between field equipment and process automation platforms.

Read more