Product Details
The Honeywell TC-ODD321 is a high-density 32-channel digital DC output module designed for use within the Honeywell Experion PKS system architecture. It distributes discrete control signals across 32 individual channels grouped into two isolated banks of 16 points per common terminal. Operating within a flexible 10 VDC to 31.2 VDC range, the unit connects to field actuators via a 36-position TC-TBCH terminal block.
Channel Grouping and Voltage Derating
The 32 channels are arranged into two groups of 16 outputs, with each group sharing a dedicated common return path. The operational output voltage depends on ambient temperature limits, supporting up to 31.2 VDC at 50 deg C with linear derating down to a maximum of 28 VDC at 60 deg C. Each output requires a minimum on-state load current of 3.0 mA to ensure reliable switching.
Electrical Output and Transient Tolerance
Under full load, the module maintains a maximum on-state voltage drop of 1 VDC at rated current per point, or up to 3 VDC under IEC 1131-2 compliance conditions. For inductive or high-inrush loads, each channel tolerates a surge current of up to 1 A for 10 ms duration, repeatable every 2 seconds at an ambient temperature of 60 deg C. Total module power dissipation is rated at 6.1 W.
| Parameter | Specification |
|---|---|
| Model | TC-ODD321 |
| Brand | Honeywell |
| Product Type | Experion DC Output Module |
| Number of Outputs | 32 channels (16 points per common) |
| Output Voltage Range | 10 VDC to 31.2 VDC @ 50 deg C (linear derating); 10 VDC to 28 VDC @ 60 deg C |
| Minimum On-State Load Current | 3.0 mA per output |
| Maximum On-State Voltage Drop | 1 VDC @ rated current per point (3 VDC for IEC 1131-2) |
| Surge Current | 1 A for 10 ms (repeatable every 2 s @ 60 deg C) |
| Power Dissipation | 6.1 W |
| Terminal Block Connection | TC-TBCH (36-position) |
| Shipping Weight | 1.5 kg |
Frequently Asked Questions
Q: What terminal block is required for field wiring on the Honeywell TC-ODD321?
A: The module requires the TC-TBCH 36-position terminal block for field wiring connections.
Q: How are the 32 output channels grouped on this module?
A: The 32 output channels are structured into two isolated banks, with 16 output points sharing a common connection per bank.
Q: What are the thermal derating conditions for the output voltage?
A: The module operates from 10 VDC to 31.2 VDC up to 50 deg C, with linear derating reducing the maximum voltage to 28 VDC at 60 deg C.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.