Skip to content

What are you looking for?


You may also like

Honeywell BC-THAI11 42622268-002 I/O Output ModuleHoneywell BC-THAI11 42622268-002 I/O Output ModuleHoneywell BC-THAI11 42622268-002 I/O Output Module
Honeywell BC-THAI11 42622268-002 I/O Output Module
Honeywell BC-THAI11 42622268-002 I/O Output Module
Honeywell BC-THAI11 42622268-002 I/O Output Module

Honeywell BC-THAI11 42622268-002 I/O Output Module


Only 10 left - Selling fast

PRODUCT SKU : BC-THAI11 42622268-002

PRODUCT TYPE : Analog Output Modules

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Honeywell BC-THAI11 42622268-002, also cataloged as the BC-THAI11 I/O Output Module, operates as a dedicated hardware component for field signal drive and analog output loop execution within Honeywell DCS platforms.

Hardware Specifications

Parameter Specification
Model BC-THAI11 (Part Number: 42622268-002)
Brand Honeywell
Origin USA
Weight 0.12 kg
Dimensions 15.2 cm x 2.4 cm x 12.6 cm
Operating Temp -40 deg C to +70 deg C
Power Consumption 2.5 W nominal
Channel Configuration High-density analog output channels
Isolation Channel-to-channel optoelectronic isolation

4-20 mA HART Loop Protocol & Channel Isolation

The BC-THAI11 module integrates 4-20 mA HART loop protocol communications across individual output channels to enable bi-directional digital signal pass-through alongside primary analog drive currents. Channel-to-channel isolation prevents ground loop interference and protects backplane bus communication from field voltage transients or cross-talk between high-density wiring loops. Integrated digital-to-analog converters maintain low thermal drift and precise signal execution under variable industrial field load impedances.

Frequently Asked Questions

Q: Can the BC-THAI11 module be hot-swapped during online system operation?

A: Yes. The module supports live insertion and removal (hot-swapping) on compatible powered backplanes, provided field wiring terminal blocks are disconnected or output loops are transferred to manual bypass prior to extraction.

Q: How does the module handle a loss of backplane communication?

A: On communication failure, internal watchdog timers trigger fail-safe hold-last-state or pre-configured fallback current logic (0 mA, 3.8 mA, or 20.5 mA) to prevent uncontrolled actuator drift.

Field Installation Guidelines

  1. Backplane Insertion: Align the module circuit board with the chassis card guides. Slide the module straight into the slot until the backplane connector fully seats, then tighten the top and bottom retention screws to ensure ground continuity.
  2. Wiring & Shielding: Terminate twisted-pair signal cables at the field terminal assembly. Earth cable shields at a single point on the cabinet ground bar to prevent ground loop noise from corrupting HART digital modulation.
  3. Loop Impedance Check: Verify that the total loop resistance (including field wiring and final control element load) remains within the specified driving voltage envelope before applying external loop power.
  4. Thermal Clearance: Maintain at least 50 mm of unobstructed vertical airflow clearance above and below the card cage assembly to ensure adequate convection cooling.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Understanding Modern SCADA Systems: Architecture, Communication Topologies, and Industrial Applications

Supervisory Control and Data Acquisition (SCADA) systems form the digital backbone of modern industrial automation. They collect critical field data, transmit signals across vast distances, and empower plant operators with real-time process visibility. Across modern infrastructures, SCADA solutions streamline centralized control and maintain continuous operational uptime.

Read more
Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

Understanding OPC Servers in Modern Industrial Automation: Principles, Architecture, and Applications

In industrial automation, connecting physical hardware with high-level software remains a primary operational challenge. Factories utilize programmable logic controllers (PLCs), distributed control systems (DCS), human-machine interfaces (HMIs), and smart sensors from diverse vendors. These devices often speak different proprietary protocols. Open Platform Communications (OPC) servers solve this interoperability challenge by standardizing how data flows across factory networks.

Read more
Industrial Fiber Optic Cables: Principles, Connectors, and Fusion Splicing Techniques

Industrial Fiber Optic Cables: Principles, Connectors, and Fusion Splicing Techniques

Modern factory automation relies heavily on fiber optic cables for high-speed industrial data transmission. Fiber optic cables transmit light pulses instead of electrical signals, eliminating electromagnetic interference (EMI) risks completely. Each optical strand consists of a high-purity glass core surrounded by a protective cladding layer. The difference in refractive index between core and cladding enables total internal reflection. Protective resin buffers, Kevlar strength members, and rugged outer jackets safeguard delicate glass cores in harsh environments. Consequently, automation engineers prefer fiber backbones for reliable noise-free communication in industrial control systems.

Read more