Skip to content

What are you looking for?


You may also like

GE IS200DRLYH1BBB Mark VI Relay Terminal BoardGE IS200DRLYH1BBB Mark VI Relay Terminal BoardGE IS200DRLYH1BBB Mark VI Relay Terminal Board
GE IS200DRLYH1BBB Mark VI Relay Terminal Board
GE IS200DRLYH1BBB Mark VI Relay Terminal Board
GE IS200DRLYH1BBB Mark VI Relay Terminal Board

GE IS200DRLYH1BBB Mark VI Relay Terminal Board


Only 10 left - Selling fast

PRODUCT SKU : IS200DRLYH1BBB

PRODUCT TYPE : Digital I/O Cards

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The GE IS200DRLYH1BBB, also cataloged as the IS200DRLY Relay Terminal Board, operates as a dedicated hardware component for relay output isolation and field contact switching within GE Mark VI platforms.

Hardware Specifications

Parameter Specification
Model IS200DRLYH1BBB
Brand GE / GE Energy
Origin USA
Operating Temp -30 to +65 deg C
Power Consumption 24 VDC Loop Powered (Backplane/I/O Pack Driven)
Relays 12 Form C Relays (24 VDC @ 3 A, 125 VDC @ 0.6 A, 120/240 VAC @ 3 A)
Power Distribution 6 Fused Branches, 1 Special Unfused Branch
Contact Protection Metal Oxide Varistor (MOV) Suppression
Field Terminals 48 Barrier Screw Terminals
I/O Redundancy Triple Module Redundant (TMR) Compatible
Mounting Type DIN Rail-Based Mount

Backplane Bus Communication Velocity and I/O Density Scaling

The IS200DRLYH1BBB terminal assembly interfaces directly with downstream I/O processor packs via high-density cable connectors. Interfacing through voted coil drive feedback paths, the board translates command logic to physical contact states while maintaining deterministic signal timing. Physical layout optimization enables structured I/O density scaling inside turbine control cabinets, preventing backplane bus communication velocity degradation and protecting processing loops from switching transients through onboard MOV suppression elements.

Frequently Asked Questions

Q: Can individual relays on the IS200DRLYH1BBB be replaced independently?

A: Yes. The board features socketed mechanical relays with transparent covers, allowing individual relay units to be extracted and replaced without desoldering the main circuit board.

Q: How does the IS200DRLYH1BBB handle output voting in redundant control configurations?

A: The board supports voted coil drive feedback, allowing Triple Module Redundant (TMR) controller configurations to drive shared relay coils via hardware logic voting structures.

Field Installation Guidelines

  1. Isolate all field power sources and disconnect control cabinet power before mounting or servicing the board.
  2. Snap the board base onto the 35 mm DIN rail inside the enclosure, verifying that spring clips lock securely into place.
  3. Establish a direct low-impedance ground connection from the panel ground stud to the earth ground terminal on the board.
  4. Wire field output loads to the 48 barrier terminal screws using spade lugs, adhering to the rated contact capacities (3 A max at 24 VDC / 120 VAC).
  5. Plug multi-pin cable harnesses into the four connector ports on the right edge of the board to establish communication with the Mark VI I/O pack.
  6. Verify fuse integrity across the 6 fused branch circuits before restoring electrical power to the system.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Will PLCs Become Obsolete? The Future of Control Systems in Industry 4.0

Will PLCs Become Obsolete? The Future of Control Systems in Industry 4.0

Modern manufacturing is undergoing a rapid technological transformation driven by Industry 4.0 innovations. Technologies like Artificial Intelligence (AI), Machine Learning (ML), and the Industrial Internet of Things (IIoT) are dominating discussions across the factory automation sector. Consequently, many engineers wonder if these advanced digital tools will eventually replace traditional Programmable Logic Controllers (PLCs). However, evaluating the core physics of industrial operations reveals a very different reality for control systems.

Read more
Demystifying Open Platform Communication (OPC): The Backbone of Industrial Interoperability

Demystifying Open Platform Communication (OPC): The Backbone of Industrial Interoperability

Interoperability remains a cornerstone requirement for modern smart factories and process automation. Open Platform Communication (OPC) bridges the gap between disparate hardware platforms, control systems, and visualization software. By establishing a universal communication standard, OPC allows field controllers, SCADA platforms, and enterprise software from different vendors to exchange real-time data seamlessly.

Read more
Understanding Siemens PLC Memory Cards: MMC, SMC, and SD Solutions in Industrial Automation

Understanding Siemens PLC Memory Cards: MMC, SMC, and SD Solutions in Industrial Automation

Memory management plays a pivotal role in maintaining control system reliability across modern manufacturing plants. Industrial control systems rely on specialized memory cards to store project logic, firmware updates, and retentive system data. Siemens uses several memory architectures, including Micro Memory Cards (MMC) and SIMATIC Memory Cards (SMC). Engineers must understand these hardware variations to ensure zero data loss and minimize downtime during maintenance routines.

Read more