The GE IC200CHS003K, also cataloged as the IC200CHS003 Input/Output Carrier, operates as a dedicated hardware component for field signal termination and backplane interface mounting within GE VersaMax control networks.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC200CHS003K |
| Brand | GE (GE Fanuc / Emerson) |
| Origin | USA |
| Weight | 0.11 kg (0.25 lbs) |
| Power Consumption | Passive backplane power routing |
| Wiring Termination Style | Connector style (36-pin connector) |
| Max I/O Points | Up to 32 input/output points |
| Rated Current Per Point | 2 A per point |
| Rated Current Power/Ground | 8 A per power and ground connection |
| Transient Voltage Rating | 300 VAC maximum |
| Contact Resistance | Less than 10 milliohms |
| Degree of Protection | IP20 |
| Housing Material | ABS plastic |
| Mounting Type | DIN rail mount (Vertical orientation) |
Deterministic Network Execution & Backplane Velocity
The IC200CHS003K carrier provides the physical backplane interface and structural mounting base for VersaMax I/O modules, establishing high-velocity backplane bus communication routes directly to the main CPU or interface unit. By managing up to 32 I/O points via an integrated 36-pin field connector, the carrier maintains contact resistance below 10 milliohms to preserve signal fidelity during real-time data acquisition cycles.
Full compatibility with Profinet / EtherNet/IP deterministic networks is achieved when paired with active network interface modules, facilitating flexible I/O density scaling across expanded rail assemblies. The mechanical architecture enforces tight firmware flash compatibility across installed field modules while providing up to 4 common power connections rated for 8 A power and ground distribution.
Frequently Asked Questions
Q: What is the maximum current capacity for individual I/O channels and power terminals on the IC200CHS003K carrier?
A: Individual I/O points are rated at 2 A per channel, while common power and ground connections support up to 8 A per point.
Q: How are field wiring connections terminated on the IC200CHS003K module?
A: Field connections are established via an integrated 36-pin connector, enabling direct harness connection rather than individual screw terminal wiring.
Q: Is live insertion or extraction of I/O modules supported on this carrier?
A: Hot-swapping depends on the system controller and module capabilities; field power and backplane supply must be isolated if non-hot-swappable modules are mounted on the carrier.
Field Installation Guidelines
- Power Isolation: Disconnect and lock out all 24 VDC/120 VAC field power and backplane power supplies before installing or servicing the carrier unit.
- DIN Rail Mounting: Snap the carrier onto a standard 35 mm DIN rail in a vertical mounting orientation, ensuring the rear locking tab fully engages the rail lip.
- Earthing and Grounding: Ensure direct metal-to-metal contact with a grounded DIN rail to establish chassis grounding for transient suppression up to 300 VAC.
- Harness Connection: Align the 36-pin field harness connector carefully with the header on the carrier and press firmly until side retaining latches lock into position.
- Module Seating: Slide the corresponding VersaMax I/O module vertically into the carrier keying tracks until the backplane connector fully mates and latching mechanisms lock.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.