Product Details

Configured for mixed analog signal processing in Foxboro I/A Series Distributed Control Systems (DCS), the Foxboro P0917QW, also cataloged as the FBM204 0-20 mA I/O Module, operates as a dedicated hardware component for 4-channel analog input and 4-channel analog output execution. It handles precision current loop signal conversion, driving field actuators and acquiring sensor inputs across isolated control loops.

Hardware Specifications

Parameter Specification
Model P0917QW (FBM204)
Brand Foxboro
Origin Consult Factory
Weight 204 g (0.45 lb)
Dimensions Height: 102 mm (114 mm with mounting), Width: 45 mm, Depth: 104 mm
Operating Temp -40 deg C to +70 deg C
Power Consumption 7 W maximum
Input Channels Four 20 mA dc analog input channels
Output Channels Four 20 mA dc analog output channels
Output Load 750 ohm maximum
Isolation Voltage 600 V ac channel-to-channel and channel-to-ground

4-20 mA HART Loop Protocol and Isolation

The module manages analog loops through channel-to-channel galvanic isolation and channel-to-ground separation, withstanding up to 600 V ac test potentials to prevent ground loops and common-mode interference. Supporting standard 4-20 mA HART loop protocol configurations, it provides accurate sigma-delta data conversion for transmitters and final control elements. This design ensures stable loop performance and protects internal backplane processors from electrical transients in harsh industrial process environments.

Frequently Asked Questions

Q: Does the P0917QW FBM204 support hot-swapping on active baseplates?

A: Yes, the module can be removed and replaced without disconnecting field device termination cabling, power, or communication wiring, subject to system cabinet safety policies.

Q: What are the input and output channel configurations of this module?

A: It features four 20 mA dc analog input channels and four 20 mA dc analog output channels.

Q: What is the maximum output load resistance supported by the analog outputs?

A: Each output channel is capable of driving into a 750 ohm maximum load.

Field Installation Guidelines

Mount the module securely onto a compatible 200 Series modular baseplate using the integrated mounting screws, ensuring proper backplane pin engagement. Verify that redundant 24 VDC power supplies are connected correctly and that field loop wiring is routed through approved termination assemblies. Terminate cable shields directly to the designated cabinet earth ground bar to maintain electromagnetic compatibility and signal integrity.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying CPU Communication Ports in Siemens PLC Architectures

Demystifying CPU Communication Ports in Siemens PLC Architectures

Industrial automation relies heavily on robust data exchange between devices. Without seamless connectivity, field instruments, network switches, human-machine interfaces, and programmable logic controllers cannot coordinate effectively. Therefore, understanding the various CPU communication ports available in Siemens hardware ensures efficient factory automation design and seamless system integration.

Read more
Mastering the Siemens PLC Scan Cycle: How the CPU Executes Automation Programs

Mastering the Siemens PLC Scan Cycle: How the CPU Executes Automation Programs

Industrial automation relies heavily on programmable logic controllers (PLCs) to manage complex manufacturing processes. Many engineers dive straight into programming without mastering the underlying architecture. However, understanding how a PLC CPU executes a program ensures reliable system design. Therefore, mastering the scan cycle optimizes both performance and troubleshooting in modern control systems.

Read more
How to Connect to Siemens S7 PLCs: 5 Essential Communication Methods

How to Connect to Siemens S7 PLCs: 5 Essential Communication Methods

Establishing a reliable hardware link between a programming terminal and a Siemens SIMATIC controller is essential for engineering workflows. Field engineers rely on distinct physical layers, ranging from legacy serial connections to high-speed Industrial Ethernet protocols. Modern factory automation environments prioritize fast data transfer and seamless driver integration. Selecting the correct connection method simplifies program downloads, online monitoring, and system troubleshooting in complex control systems.

Read more