Skip to content

What are you looking for?


You may also like

Emerson KJ4006X1-BL1 8-Channel Terminal BlockEmerson KJ4006X1-BL1 8-Channel Terminal BlockEmerson KJ4006X1-BL1 8-Channel Terminal Block
Emerson KJ4006X1-BL1 8-Channel Terminal Block
Emerson KJ4006X1-BL1 8-Channel Terminal Block
Emerson KJ4006X1-BL1 8-Channel Terminal Block

Emerson KJ4006X1-BL1 8-Channel Terminal Block


Only 10 left - Selling fast

PRODUCT SKU : KJ4006X1-BL1

PRODUCT TYPE : Termination Blocks

PRODUCT VENDOR : EMERSON


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for high-density field wiring integration within DeltaV DCS platforms, the Emerson KJ4006X1-BL1 (KJ4006X1-BL1 Terminal Block) provides direct physical signal termination for 8 analog input channels with user-configurable 2/4-wire support.

Hardware Specifications

Parameter Specification
Model KJ4006X1-BL1
Brand Emerson
Origin Subject to factory shipping documentation
Weight 0.2 kg
Dimensions 100 mm x 50 mm x 25 mm
Operating Temp -40 deg C to 70 deg C
Power Consumption Passive interconnect component
Channels 8 Analog Input Channels
Signal Range -10 V to +10 V or 4 mA to 20 mA
Input Impedance 10 kO (typical)
Isolation Voltage 1500 VDC between channels and field power

4-20 mA HART Loop Protocol Connectivity

The KJ4006X1-BL1 acts as the primary interface module for field instrumentation in DeltaV systems, supporting both voltage and current signaling. The terminal block is designed to accommodate 4-20 mA HART loop protocol signals, enabling seamless communication between smart field transmitters and the DCS controller. The architecture ensures 1500 VDC isolation between individual channels and the field power supply, minimizing the risk of ground loops and common-mode interference. This passive termination design maintains signal loop integrity while conforming to the ISA-S71.04 Class G3 standard for airborne contaminants, ensuring longevity in harsh process environments.

Frequently Asked Questions

Q: Is this terminal block compatible with both 2-wire and 4-wire field device configurations?

A: Yes. The terminal block is user-configurable to support both 2-wire and 4-wire analog input loops, allowing for flexible integration with various transmitter types.

Q: What is the isolation level provided by this terminal block?

A: The device provides 1500 VDC isolation between the input channels and the field power circuit, ensuring significant protection against electrical interference and ground loop potential in the I/O loop.

Field Installation Guidelines

  1. Mounting: Secure the terminal block to the I/O carrier interface. Ensure all connection pins are properly aligned before applying pressure to engage the backplane connector.
  2. Wiring: For 4-20 mA signals, utilize shielded twisted-pair cables. Terminate the shield at the ground terminal provided on the carrier to effectively shunt high-frequency noise.
  3. Powering: Verify field power input complies with the specified limits (30 VDC for nL/ic or 60 VDC for ec installations) before finalizing the loop connections.
  4. Environment: While the block is rated for -40 deg C to 70 deg C, ensure the installation area is free from excessive vibration beyond the 0.7g limit to prevent loosening of terminal screws.
  5. Validation: Upon installation, verify the loop continuity and impedance at the terminal points prior to powering the I/O card to prevent potential damage to the input stage of the DCS module.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Demystifying Programmable Logic Controllers: Comprehensive Guide to PLC Classification and Selection in Industrial Automation

Demystifying Programmable Logic Controllers: Comprehensive Guide to PLC Classification and Selection in Industrial Automation

Modern industrial automation heavily relies on Programmable Logic Controllers (PLCs) to drive factory floor efficiency. Over my 15 years as an industrial automation expert working with DCS, TSI, and control systems, I have seen PLCs evolve into the central nervous system of modern manufacturing. Selecting the right controller requires a deep understanding of PLC types based on physical size, hardware architecture, and power supply configurations.

Read more
Comprehensive Guide to PLC Types in Modern Industrial Automation

Comprehensive Guide to PLC Types in Modern Industrial Automation

Modern industrial automation relies on programmable logic controllers to govern critical factory operations. System integrators classify PLCs based on scale, hardware architecture, and power supply design. Understanding these core categories enables automation engineers to select the right control system architecture. Consequently, proper hardware selection optimizes performance while minimizing long-term operational costs.

Read more
Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Demystifying the DDE Protocol in Legacy Industrial Automation Systems

Modern control systems rely heavily on seamless interprocess communication to exchange operational data between software programs. Microsoft first introduced the Dynamic Data Exchange (DDE) protocol in 1987 to enable real-time data sharing. In factory automation, DDE served as an early bridge between control software and Windows desktop applications. Therefore, understanding DDE mechanics provides crucial insights into how legacy industrial networks established software-level connectivity.

Read more