PRODUCT SKU : 330103-08-13-05-02-00

PRODUCT TYPE : Proximity Probes

PRODUCT VENDOR : Bently Nevada


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The 330103-08-13-05-02-00 is a metric 8 mm eddy-current proximity probe from the Bently Nevada 3300 XL series, engineered for precise shaft displacement and vibration measurements. This transducer interfaces with compatible Proximitor sensors to deliver reliable gap voltage signals for critical rotating machinery protection systems.

Model Configuration and Suffix Breakdown

The ordering part number encodes specific physical and electrical configuration options defined by the manufacturer matrix. The base model designates the metric M10 x 1 thread design without protective armor. Suffix options dictate the unthreaded body length, case dimensions, and cable parameters.

Mechanical Construction and Materials

The probe features a durable polyphenylene sulfide (PPS) tip combined with AISI 303 or 304 stainless steel housing. Viton O-ring seals provide reliable differential pressure protection across the mounting interface.

Electrical Performance and Environmental Ratings

The sensor delivers a 2 mm linear range starting at 0.25 mm from the target surface, operating with a nominal DC resistance of 7.45 ohms. It is rated for temperatures ranging from -52 deg C to +177 deg C while maintaining environmental stability under high humidity conditions.

Hardware Specifications

Parameter Specification
Model 330103-08-13-05-02-00
Brand Bently Nevada
Product Family 3300 XL Proximity Transducer System
Thread Type M10 x 1
Unthreaded Length 80 mm
Overall Case Length 130 mm
Total Cable Length 0.5 m
Connector Type Miniature coaxial ClickLoc
Linear Range 2 mm (80 mils)
Nominal DC Resistance 7.45 ohms ± 0.50
Operating Temperature -52 deg C to +177 deg C (-62 deg F to +350 deg F)
Agency Approvals Standard configuration (non-hazardous)
Probe Weight 323 g/m (11.4 oz per meter)

Frequently Asked Questions

Q: What is the recommended gap setting for radial vibration monitoring?

A: The recommended radial vibration gap is set to -9 Vdc, corresponding to approximately 1.27 mm (50 mils) from the target surface.

Q: What thread type and unthreaded length are specified by this model?

A: This model features an M10 x 1 metric thread with an 80 mm unthreaded length designated by option code 08.

Q: Does this configuration include hazardous area approvals?

A: No, option code 00 indicates a standard configuration for non-hazardous installations.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Securing Remote Access Tools in Industrial Automation Environments

Securing Remote Access Tools in Industrial Automation Environments

Remote access has evolved from a convenient support option into an indispensable component of modern industrial automation. Consequently, control engineers routinely leverage remote connectivity for PLC programming, DCS diagnostics, and commissioning support to minimize costly plant downtime. However, poorly managed remote access tools—such as shared credentials, always-on sessions, or unsecured cloud relays—create dangerous vulnerabilities in critical control systems. In my 15 years of commissioning industrial automation networks, I have witnessed how inadequate perimeter security exposes factory floors to severe cyber threats. Below, I evaluate the leading remote access solutions and highlight how organizations can secure their operational technology (OT) infrastructure.

Read more
Achieving Deterministic Industrial Networks Through Time-Sensitive Networking (TSN)

Achieving Deterministic Industrial Networks Through Time-Sensitive Networking (TSN)

Industrial automation environments increasingly demand high-speed, deterministic data transmission to coordinate complex machinery and factory automation lines. Therefore, control engineers continually seek networking technologies that eliminate unpredictable latency and packet loss. In my 15 years of commissioning distributed control systems (DCS) and high-speed motion networks, I have witnessed how traditional Ethernet bottlenecks can trigger unforced production stops. Below, I explore how Time-Sensitive Networking (TSN) transforms standard Ethernet into a deterministic communication backbone.

Read more
Comparing PID and Model Predictive Control (MPC) in Industrial Automation

Comparing PID and Model Predictive Control (MPC) in Industrial Automation

Advanced process control strategies remain fundamental for maintaining optimal plant efficiency and product quality. Therefore, control engineers frequently evaluate whether a traditional Proportional-Integral-Derivative (PID) algorithm or a Model Predictive Control (MPC) strategy suits a given application. In my 15 years of commissioning distributed control systems (DCS) and factory automation networks, I have tuned thousands of PID loops while deploying complex MPC packages on multivariable distillation columns. Below, I break down the core operational differences between these two foundational control methodologies.

Read more