Allen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output ModuleAllen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output ModuleAllen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output Module
Allen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output Module
Allen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output Module
Allen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output Module

Allen Bradley 1756-OF8IK ControlLogix 8-Channel Isolated Analog Output Module


Only 10 left - Selling fast

PRODUCT SKU : 1756-OF8IK

PRODUCT TYPE : Analog Output Module

PRODUCT VENDOR : Allen-Bradley


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Overview

The Allen Bradley 1756-OF8IK functions as a high-performance, isolated analog output module for the ControlLogix platform. It provides eight independent current output channels to drive field devices such as actuators, valves, and motor controllers. This specific model features factory-applied conformal coating (indicated by the "K" suffix), which provides essential protection against corrosive atmospheres and humidity. By utilizing channel-to-channel isolation, the 1756-OF8IK eliminates ground loop interference and ensures high-integrity signal delivery in complex industrial environments.

Technical Specifications

Feature Detailed Specification
Manufacturer Allen Bradley / Rockwell Automation
Part Number 1756-OF8IK
Module Type Isolated Analog Output (Current)
Number of Outputs 8 Channels (Individually Isolated)
Output Range 0–20 mA or 4–20 mA
Resolution 15 Bits
Output Voltage Range 5–30V DC
Current Draw (24V DC) 400 mA
Power Dissipation 6.5 Watts
Isolation Voltage 50V Continuous
Removable Terminal Block 1756-TBNH, 1756-TBSH
Condition 100% Brand New Original

Engineering Advantages

  • Channel-to-Channel Isolation: The 1756-OF8IK isolates each of its eight outputs individually. This prevents electrical noise and ground loops from propagating between loops, solving common signal distortion issues in large-scale facilities where field devices reside at different potential levels.

  • Conformal Coating for Harsh Service: The "K" version includes a specialized protective layer over the internal circuitry. This barrier resists chemical vapors, salt spray, and moisture, making this module the mandatory choice for wastewater treatment, oil and gas, and chemical processing plants.

  • High-Resolution Control: The 15-bit digital-to-analog converter ensures granular control over current loops. This precision allows the PLC to modulate control valves with extreme accuracy, optimizing process efficiency and reducing mechanical wear caused by "stepped" movements.

  • Robust Fault Containment: Channel isolation ensures that a short circuit or electrical fault on one field device does not impact the remaining seven channels. This containment strategy minimizes system downtime and protects the overall integrity of the ControlLogix chassis.

  • Simplified Maintenance: The module utilizes standard 1756-TBNH or 1756-TBSH terminal blocks. Maintenance teams can replace the module without disconnecting field wires, significantly reducing the Mean Time to Repair (MTTR) during critical hardware swaps.

FAQs

  • Is the 1756-OF8IK 100% Brand New?

    Yes. We supply this module as 100% Brand New in original factory-sealed packaging. This ensures the conformal coating is fully intact and the hardware meets the latest OEM specifications.

  • Can the 1756-OF8IK drive voltage loads?

    This specific model is optimized for current outputs (0–20mA or 4–20mA). For applications requiring ±10V voltage outputs, we recommend selecting the 1756-OF8 or the isolated 1756-OF6VI models.

  • Does the module require an external power supply?

    Yes, the module draws 400 mA at 24V DC from the backplane or an external user-supplied 24V source to power the isolated current loops. Ensure your chassis power supply has sufficient headroom for the 6.5W dissipation.

  • What is the difference between 1756-OF8I and 1756-OF8IK?

    The "K" suffix in 1756-OF8IK indicates the addition of conformal coating. Both modules share identical electrical performance, but the "K" model provides superior resistance to environmental corrosion.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding VFD Mechanical Brake Logic and Control in Industrial Automation

Understanding VFD Mechanical Brake Logic and Control in Industrial Automation

Variable Frequency Drives (VFDs) play a crucial role in modern industrial automation by controlling motor speed, torque, and acceleration. However, high-inertia loads and vertical lifting systems require precise mechanical braking logic to ensure operational safety and prevent equipment damage.

Read more
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more