Product Details

Configured for 16-channel analog and digital field signal termination in Yokogawa CENTUM VP/CS and ProSafe-RS control architectures, the YOKOGAWA TE16*B (TE16 Terminal Block Module) provides direct physical signal execution. It routes wiring from field transmitters and actuators directly to system I/O modules, maintaining signal path continuity inside industrial control cabinets.

Hardware Specifications

Parameter Specification
Model TE16*B
Brand YOKOGAWA
Origin Japan
Weight 0.30 kg
Dimensions 130 x 45 x 85 mm
Operating Temp -20 to 60 deg C
Power Consumption Passive (0 W)
System Compatibility CENTUM VP/CS, ProSafe-RS
Channel Count 16 points / channels
Signal Types 4-20 mA analog input/output, discrete digital signals
Wire Termination Screw clamp terminals

Channel-to-Channel Isolation and 4-20 mA HART Signal Conditioning

The TE16*B interface architecture facilitates structured cable distribution for 4-20 mA HART loop configurations and discrete digital lines across DCS and SIS platforms. Channel-to-channel isolation principles prevent ground loop currents from distorting precision analog process measurements during multi-point field deployments. The internal trace geometry maintains low loop impedance, suppressing electromagnetic noise coupling between adjacent termination points.

Frequently Asked Questions

Q: What conductor gauge range does the TE16*B terminal block accept?

A: The screw clamp terminals accept solid or stranded copper conductors ranging from 0.2 mm2 to 2.5 mm2 (AWG 24 to AWG 14).

Q: Can the TE16*B module handle mixed analog and digital field signals on the same terminal strip?

A: Yes, the 16 channels accommodate both 4-20 mA analog loops and low-voltage digital signals, provided proper physical separation guidelines are observed inside the wiring duct to prevent inductive coupling.

Q: Is external power required to operate the TE16B terminal block?

A: No, the TE16B functions as a passive termination assembly, conducting signal currents directly between field instruments and the system I/O interface without internal power draw.

Field Installation Guidelines

Disconnect all loop power sources and control cabinet main breakers before connecting field wiring to the TE16*B module. Secure the terminal block to the panel mounting plate or DIN rail using specified mechanical fasteners. Strip field conductor insulation to 7 mm and tighten screw terminals to a maximum torque of 0.5 Nm to maintain solid conductivity without damaging wire strands. Ground all cable shields at a single point on the main instrument ground bar. Maintain a minimum separation distance of 100 mm between low-voltage signal cables and high-voltage AC power lines.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more
Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial automation relies heavily on robust networking infrastructure to connect programmable logic controllers (PLCs), distributed control systems (DCS), and human-machine interfaces (HMIs). Modern factory automation environments generate vast amounts of real-time operational data across deterministic networks. Understanding the structural differences between hubs, switches, and routers ensures optimal traffic segmentation, minimizes latency, and maintains high network availability.

Read more
Safety Relays in Industrial Automation: Fundamentals, Design Standards, and Fail-Safe Architecture

Safety Relays in Industrial Automation: Fundamentals, Design Standards, and Fail-Safe Architecture

Safety relays form the bedrock of functional safety in modern factory automation, preventing catastrophic equipment failure and protecting plant personnel. While standard electromechanical relays handle basic load switching, they lack the redundant diagnostics required for high-risk industrial environments. Modern industrial automation platforms—including programmable logic controllers (PLCs) and distributed control systems (DCS)—rely on specialized safety relays to monitor field devices and isolate hazards instantly.

Read more