Skip to content

What are you looking for?


You may also like

AAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input ModuleAAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input ModuleAAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input Module
AAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input Module
AAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input Module
AAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input Module

AAI135-S00/K4A00 | Yokogawa CENTUM VP Isolated Current Input Module


Only 10 left - Selling fast

PRODUCT SKU : AAI135-S00/K4A00

PRODUCT TYPE : Isolated Current Input Module

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Overview

The Yokogawa AAI135-S00/K4A00 functions as a reliable 16-channel isolated current input interface for the CENTUM VP and CS 3000 integrated production control systems. This module captures standard 4 to 20 mA DC signals from field transmitters, providing the essential data link for process monitoring and automated control loops. By utilizing high-speed signal processing and robust channel-to-system isolation, it maintains precise data flow even in electrically noisy industrial environments.

Part Number Breakdown: AAI135-S00/K4A00

Yokogawa employs a modular suffix system to define the specific electrical and physical attributes of each I/O card:

  • AAI135: Base model for Isolated Current Input (4 to 20 mA, 16-channel).

  • -S: Standard type performance specification for general process control.

  • 0: Standard type with no explosion protection (General Purpose).

  • 0: Basic functional specification for standard operating environments.

  • /K4A00: Equipped with the KS cable interface adapter, designed for seamless connection to AEA4D terminal boards via specialized system cables.

Technical Specifications

We supply this module in 100% brand new, original factory condition to ensure full compliance with your system's MTBF requirements.

Feature Specification
Number of Channels 16-channel, isolated
Input Signal Range 4 to 20 mA DC
Allowable Input Current 25 mA DC
Withstanding Voltage 500 V AC (between input and system)
Interface Style KS Cable Interface (/K4A00)
Weight Approximately 0.35 kg

Engineering Advantages

  • Optimized Signal Isolation: The AAI135-S00 provides 500 V AC isolation between the field inputs and the internal system bus. This barrier prevents ground loops and protects the expensive FIO (Field network I/O) nodes from field-side electrical surges.

  • Simplified System Integration: The /K4A00 KS cable interface eliminates the need for individual terminal-by-terminal wiring at the module level. This plug-and-play approach reduces installation time and minimizes the risk of wiring errors during commissioning.

  • High-Density Monitoring: 16 isolated channels in a single slot allow for maximum I/O density within the cabinet. This helps reduce the total number of I/O nodes required, lowering both hardware costs and the physical footprint of the control room.

  • Redundancy Support: When installed in a redundant configuration, the module supports seamless failover. If the active module detects an internal hardware failure, the system automatically switches to the standby module without interrupting the 4-20 mA process signal.

FAQs

  • Can I use the AAI135-S00/K4A00 for 2-wire transmitter power?

    The AAI135 series typically acts as a signal receiver (sink). If your 2-wire transmitters require loop power directly from the I/O module, you should verify if your field wiring includes an external 24 V DC supply or consider the AAI143 series which provides integrated loop power.

  • What is the benefit of the KS cable interface (/K4A00) over a terminal block?

    The KS cable interface allows you to move the termination point to a separate AEA4D terminal board. This simplifies cabinet organization, makes cable management much cleaner, and allows for faster module replacement during maintenance.

  • Is this module compatible with older CENTUM CS 3000 software?

    Yes, the AAI135 is a legacy-friendly module that maintains compatibility across multiple generations of Yokogawa DCS software, provided the appropriate I/O definitions are loaded in the system builder.

  • Does this module support HART communication?

    The AAI135-S00 is a standard analog input module and does not support HART digital signal pass-through. For HART-compatible applications, the AAI141 or AAI143 series are the recommended alternatives.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Evolving SCADA System Architectures in Industrial Automation

Evolving SCADA System Architectures in Industrial Automation

A robust Supervisory Control and Data Acquisition (SCADA) system serves as the heartbeat of modern industrial operations. Understanding SCADA system architecture is vital for engineers designing efficient control systems. These architectures have evolved from isolated, monolithic structures to highly interconnected, networked ecosystems. Choosing the right design requires balancing data visibility, processing power, and long-term scalability requirements.

Read more
Choosing the Right Controller: PLC vs. Motion Controller in Industrial Automation

Choosing the Right Controller: PLC vs. Motion Controller in Industrial Automation

Selecting the optimal control architecture is a foundational decision in industrial automation. Engineers must frequently choose between a Programmable Logic Controller (PLC) and a dedicated Motion Controller. While both systems manage machinery, their underlying design philosophies differ significantly, impacting performance, scalability, and system integration.

Read more
Mastering PLC Power Supply Architectures and Operating Voltages

Mastering PLC Power Supply Architectures and Operating Voltages

Selecting the correct operating voltage is a critical step in designing reliable industrial automation systems. Whether you are working with a compact PLC or a large-scale DCS, your power architecture dictates the system's longevity. In this guide, we explore the standard voltage ranges and power distribution strategies required to maintain stable factory automation operations.

Read more