Skip to content

What are you looking for?


You may also like

ABB SS822Z 3BSC610055R1 Power Voting UnitABB SS822Z 3BSC610055R1 Power Voting UnitABB SS822Z 3BSC610055R1 Power Voting Unit
ABB SS822Z 3BSC610055R1 Power Voting Unit
ABB SS822Z 3BSC610055R1 Power Voting Unit
ABB SS822Z 3BSC610055R1 Power Voting Unit

ABB SS822Z 3BSC610055R1 Power Voting Unit


Only 10 left - Selling fast

PRODUCT SKU : SS822Z 3BSC610055R1

PRODUCT TYPE : Power Voting Modules

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB SS822Z 3BSC610055R1, also cataloged as the SS822Z Power Voting Unit, operates as a dedicated hardware component for dual-redundant 24 VDC power supply voting and load sharing within ABB System 800xA platforms.

Hardware Specifications

Parameter Specification
Model SS822Z (3BSC610055R1)
Brand ABB
Origin Sweden
Weight 0.50 kg
Dimensions 120 mm x 100 mm x 40 mm
Operating Temp -25 to 70 deg C
Power Consumption Passive Diode ORing (< 5 W internal dissipation)
Input Voltage 24 VDC Nominal (19.2 to 30.0 VDC range, Dual Inputs)
Output Current Rating 20 A total continuous output
Module Category Power Voting Modules
System Platform ABB System 800xA / AC 800M

Deterministic Network Integration and I/O Density Scaling

The SS822Z power voting unit couples dual 24 VDC power sources via low-loss Schottky diode isolation circuits, delivering continuous power feeds to central controller racks and field communications interface modules. The unit maintains stable power delivery to Profinet and EtherNet/IP deterministic networks during primary power supply failure events without output voltage drops. High I/O density scaling across AC 800M controller cabinets is supported by minimizing panel space consumption, while signal continuity maintains uncorrupted backplane bus communication velocity and continuous firmware flash compatibility during online system maintenance.

Frequently Asked Questions

Q: Can the SS822Z power voting unit be hot-swapped while the 24 VDC system load is fully energized?

A: Yes, if a parallel redundant voting module configuration is deployed; otherwise, isolated input connections must be disconnected individually to prevent output voltage disruption.

Q: How does the SS822Z isolate a short-circuited primary power supply from the DC bus?

A: Internal low-impedance reverse-blocking diodes prevent reverse current flow from the healthy power supply into the faulted input rail.

Q: What relay contact outputs are provided on the SS822Z for status monitoring?

A: The module contains dry alarm contacts that change state when either of the two 24 VDC input voltages drops below the operational threshold.

Field Installation Guidelines

  • Mount the module vertically on standard 35 mm DIN rails to allow free air convection across the cooling heatsink slots.
  • Maintain a minimum vertical clearance of 50 mm above and below the unit to prevent thermal throttling under maximum continuous load.
  • Torque power input and output screw terminals to 0.5 Nm using appropriately rated copper conductors (minimum 2.5 mm squared).
  • Connect the functional grounding conductor directly to the panel earth busbar with low-impedance copper grounding strap to maintain transient surge protection.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Hub vs Switch vs Router in Industrial Automation Architecture

Hub vs Switch vs Router in Industrial Automation Architecture

Modern factory automation relies on reliable industrial networking infrastructure to exchange real-time field data across operational technology systems. Engineers often encounter networking hardware like hubs, switches, and routers when integrating Programmable Logic Controllers, Distributed Control Systems, and SCADA monitoring nodes. Although these devices share physical ports, they operate at different layers of the Open Systems Interconnection reference model and deliver distinct traffic management capabilities.

Read more
Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling cabinets serve as the vital interface between field instrumentation and control room electronics in modern process facilities. Regular preventive maintenance of these cabinets ensures signal integrity across programmable logic controllers (PLCs), distributed control systems (DCS), and emergency shutdown (ESD) networks. System technicians must execute structured inspection protocols to mitigate environmental risks, identify loose wiring, and maintain continuous operational readiness.

Read more
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more