Product Details

Configured for generator synchronization and phase alignment in parallel power systems, the Woodward 9907-028 (9907-028 Synchronizer) provides direct physical/electrical execution of generator speed matching and breaker closure signaling.

Hardware Specifications

Parameter Specification
Model 9907-028
Brand Woodward
Weight 2.2 kg (5 lbs)
Dimensions Not specified
Operating Temp -45 to 70 deg C
Power Consumption 5 W
Voltage Input 115/230 VAC RMS (+/- 10%)
Frequency 50/60 Hz
Phase Angle +/- 10 deg

Actuator Loop Feedback Response

The 9907-028 synchronizer modulates prime mover rotational speed to align the generator phase angle within a +/- 10 deg window relative to the bus. To achieve a stable actuator loop feedback response, the device integrates adjustable dynamic settings that allow for precise tuning of the frequency correction output. The controller interfaces with external speed governors, such as the 2301 or EPG series, to influence engine speed without performing voltage matching. The internal logic provides four selectable operational modes—RUN, CHECK, PERMISSIVE, and OFF—which dictate the synchronization behavior and the activation of the circuit breaker closure signals.

Frequently Asked Questions

Q: Does the 9907-028 perform automatic voltage matching during synchronization?

A: No, this model does not feature voltage matching capabilities. It focuses exclusively on phase angle and frequency matching to facilitate parallel operation.

Q: How do the different operational modes (RUN, CHECK, PERMISSIVE) affect synchronization?

A: RUN mode enables full synchronization and breaker closure signals. CHECK mode performs synchronization calculations but inhibits breaker closure. PERMISSIVE mode allows synchronization monitoring but restricts the unit from modifying the engine speed.

Field Installation Guidelines

  1. Mounting: Install the synchronizer within a switchgear enclosure. Ensure adequate ventilation to maintain operation within the rated -45 to 70 deg C range, though optimal stability is observed between 10 deg C and 30 deg C.
  2. Wiring: Use shielded cabling for all sensing inputs (bus/generator voltage) and control outputs to prevent electrical noise interference.
  3. Switch Configuration: Install a user-defined multi-position switch to toggle between the four operational states. Verify the wiring of the switch inputs corresponds to the desired mode definitions (RUN, CHECK, PERMISSIVE, OFF).
  4. Validation: During initial commissioning, monitor the phase angle error and frequency drift. Adjust internal dynamic settings as necessary to achieve smooth synchronization without excessive speed hunting or oscillation before breaker closure.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more
Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial automation relies heavily on robust networking infrastructure to connect programmable logic controllers (PLCs), distributed control systems (DCS), and human-machine interfaces (HMIs). Modern factory automation environments generate vast amounts of real-time operational data across deterministic networks. Understanding the structural differences between hubs, switches, and routers ensures optimal traffic segmentation, minimizes latency, and maintains high network availability.

Read more
Safety Relays in Industrial Automation: Fundamentals, Design Standards, and Fail-Safe Architecture

Safety Relays in Industrial Automation: Fundamentals, Design Standards, and Fail-Safe Architecture

Safety relays form the bedrock of functional safety in modern factory automation, preventing catastrophic equipment failure and protecting plant personnel. While standard electromechanical relays handle basic load switching, they lack the redundant diagnostics required for high-risk industrial environments. Modern industrial automation platforms—including programmable logic controllers (PLCs) and distributed control systems (DCS)—rely on specialized safety relays to monitor field devices and isolate hazards instantly.

Read more