Configured for signal termination and distribution in Mark VIe control architectures, the GE IS200TCASH1ACB (IS200TCASH1ACB Terminal Board) provides direct physical and electrical execution of analog signal routing and sensor excitation.

Hardware Specifications

Parameter Specification
Model IS200TCASH1ACB
Brand General Electric
Origin USA
Weight 2 lbs
Dimensions 33.02 cm x 17.8 cm
Operating Temp 30 deg C to 50 deg C
Power Consumption 24 VDC (Excitation)
Analog Inputs 25
Analog Outputs 4-20 mA / 0-20 mA
Lead Resistance 15 Ohm (Maximum)

Profinet / EtherNet/IP Deterministic Networks

The IS200TCASH1ACB serves as an interface node within the Mark VIe ecosystem, facilitating standardized signal conditioning between field-mounted instrumentation and system I/O packs. The board architecture supports deterministic backplane bus communication velocity, ensuring that analog data acquisition remains synchronized with controller scan cycles. Firmware flash compatibility is managed via the host I/O pack configuration, which defines the scaling and filtering parameters for the 25 input channels. The module supports I/O density scaling through its robust termination layout, allowing for high-integrity signal transmission while minimizing signal degradation over field cabling. The surface-mount technology utilized in the PCB construction maintains consistent electrical impedance, supporting precision analog output regulation from 0 to 20 mA.

Frequently Asked Questions

Q: Does the IS200TCASH1ACB support hot-swapping under load?

A: No. Replacement of the terminal board requires the associated I/O loop to be de-energized to prevent transient currents from damaging the analog output circuitry or the connected field devices.

Q: Is the 24 VDC excitation voltage configurable on a per-channel basis?

A: No. The 24 VDC excitation is common across the designated input channels on the board. Ensure all field instruments connected to these inputs are compatible with the shared excitation voltage.

Field Installation Guidelines

  1. Mounting: Secure the board within the cabinet using the provided mounting holes. Maintain adequate clearance from high-voltage AC lines to prevent induced noise on the analog signal paths.
  2. Wiring: Terminate field wiring using the designated terminal blocks. Maintain consistent polarity for all analog loops and ensure that cable shields are grounded at a single, low-impedance point to minimize common-mode noise.
  3. Loop Resistance: Ensure that the total lead resistance of the field cabling does not exceed 15 Ohm to maintain the accuracy of the 4-20 mA signal transmission.
  4. Environment: Verify that the cabinet internal temperature remains within the specified range of 30 deg C to 50 deg C. Provide sufficient airflow to prevent heat accumulation around the board's passive and active components.
  5. Verification: Prior to energization, conduct a point-to-point electrical check to verify wiring integrity and polarity. Use the Mark VIe diagnostic tool to confirm that all 25 analog inputs are correctly registered by the system.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
Mastering Modern Industrial Joystick Controls in Heavy Automation

Mastering Modern Industrial Joystick Controls in Heavy Automation

Industrial joysticks play a pivotal role in human-machine interaction across heavy material handling and mobile hydraulics. These tactile controllers translate complex operator movements into precise electrical signals for PLCs, motion controllers, and DCS networks. Consequently, selecting and installing the right joystick architecture ensures operator safety, reduces fatigue, and optimizes equipment performance.

Read more
Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Modern manufacturing relies heavily on automated control systems to maximize throughput and maintain product quality. However, unplanned downtime in industrial automation can cost facility operators thousands of dollars per hour. Understanding how programmable logic controllers (PLCs), distributed control systems (DCS), and field instrumentation fail empowers engineering teams to implement robust preventive maintenance strategies.

Read more