Skip to content

What are you looking for?


You may also like

Foxboro FBM214 P0916BX I/A Series HART Input ModuleFoxboro FBM214 P0916BX I/A Series HART Input ModuleFoxboro FBM214 P0916BX I/A Series HART Input Module
Foxboro FBM214 P0916BX I/A Series HART Input Module
Foxboro FBM214 P0916BX I/A Series HART Input Module
Foxboro FBM214 P0916BX I/A Series HART Input Module

Foxboro FBM214 P0916BX I/A Series HART Input Module


Only 10 left - Selling fast

PRODUCT SKU : FBM214 P0916BX

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : Foxboro


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Foxboro FBM214 P0916BX HART Input Module Terminal Assembly

The Foxboro FBM214 P0916BX, also cataloged as the FBM214 HART Communication Input Interface Module, operates as a dedicated hardware component for 8-channel analog input acquisition and HART signal processing within Foxboro I/A Series 200 Series platforms.

Hardware Specifications

Parameter Specification
Model FBM214 P0916BX
Brand Foxboro / Schneider Electric
Origin USA
Weight 284 g (Module) / 3.00 lbs (TA)
Dimensions 102 mm x 45 mm x 104 mm
Operating Temp -20 to +70 deg C
Power Consumption 7 W Maximum
System Platform Foxboro I/A Series 200 Series
Input Channels 8 analog input channels (0-20 mA DC)
Analog Accuracy +/-0.03% of full scale (15-bit resolution)
Communication Speed 1200 baud (HART FSK, 2 messages/second)
Isolation Voltage Group-isolated (isolated from ground and module logic)

4-20 mA HART Loop Protocol & Channel-to-Channel Isolation

The FBM214 P0916BX incorporates integrated 24 VDC transmitter power distribution across its 8 analog channels to drive field-side 4-20 mA current loops. The module extracts digital HART Frequency Shift Keying (FSK) signals superimposed on the analog current, processing secondary variables and diagnostic data at a rate of 2 messages per second per channel. Galvanic group isolation isolates the field wiring from the internal module logic and ground bus, preventing common-mode noise and ground loops from compromising the 15-bit sigma-delta data conversion on the redundant 2 Mbps Module Fieldbus.

Frequently Asked Questions

Q: What is the physical relationship between the FBM214 and the P0916BX part number?

A: The FBM214 designates the 8-channel electronic input module, whereas P0916BX specifies the DIN-rail mounted 3-tier PVC compression Field Termination Assembly (FTA) that connects to the module via a 25-pin male D-subminiature cable.

Q: What are the input resistance and signal filtering specs for the analog current loop?

A: The input circuit provides a nominal sense resistance of 61.9 ohms (280 ohms minimum total input resistance) with a channel update rate of 100 ms and rejection ratings exceeding 100 dB common-mode and 95 dB normal-mode at 50/60 Hz.

Field Installation Guidelines

Mount the P0916BX termination assembly on a standard 32 mm or 35 mm DIN rail inside the field enclosure. Route the 8-channel 4-20 mA transmitter field wiring to the 3-tier compression terminal block, ensuring signal wire shields terminate at the cabinet earth ground point. Connect the termination assembly to the FBM214 baseplate interface using a dedicated Type 1 25-pin D-sub cable, keeping cable lengths within the maximum 30 m limit to prevent signal attenuation and preserve HART FSK communication integrity.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.